3 Basic Instructions

DVP-PLC Application Manual

3-8

When the SET instruction is driven, its designated device will be “On” and keep being On both when SET instruction

is still being driven or not driven. Use RST instruction to set “Off” the device.

Program Example:

Ladder diagram:

Instruction code:

Operation:

LD

X0

Loading in contact A of X0

ANI

Y0

Connecting to contact B of Y0 in series

X0

Y0

Y1

SET

SET

Y1

Y1 latched (On)

Mnemonic Function Program

steps

RST

Clear the contacts or the registers

1

Controllers

ES

EX

SS

SA

SX

SC

EH

SV

X0 ~ X377 Y0 ~ Y377 M0 ~ M4095 S0 ~ S1023 T0 ~ T255 C0 ~ C255 D0 ~ D9999

E0 ~ E7

F0 ~ F7

Operand

-

9

9

9

9

9

9

9

Explanations:

1. When the RST instruction is driven, the actions of the designated devices are:

Device

Status

Y, M, S,

Coil and contact will be set to “Off”

T, C

Present values of the timer or counter will be set to “0”, and the coil and contact will be set to
“Off”

D, E, F

The content will be set to “0”.

2. If RST instruction is not being executed, the status of the designated device will stay intact.

Program Example:

Ladder diagram:

Instruction code:

Operation:

LD

X0

Loading in contact A of X0

X0

Y5

RST

RST

Y5

Resetting contact Y5

Mnemonic Function Program

steps

TMR

16-bit timer

1

Controllers

ES

EX

SS

SA

SX

SC

EH

SV

T-K

T0 ~ T255, K0 ~ K32,767

Operand

T-D

T0 ~ T255, D0 ~ D9999

Explanations:

When TMR instruction is executed, the designated coil of the timer will be On and the timer will start to time. When the

set value in the timer is reached (present ≥ set value), the contact will be:

NO (Normally Open) contact

Open collector

NC (Normally Closed) contact

Close collector