beautypg.com

2 functions of devices in dvp-plc – Delta Electronics Programmable Logic Controller DVP-PLC User Manual

Page 63

background image

2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-35

Special

M

Function

ES

EX

SS

SA

SX

SC

EH

EH2

SV

Off

Ø

On

STOP

Ø

RUN

RUN

Ø

STO

P

Attribute Latched Default

M1030*

ES/SA: Y1 pulse output of PLSY, PLSR instructions
is completed, or other relevant instructions complete
their executions.

EH/EH2/SV: the 2

nd

group pulse output CH1 (Y2,

Y3) is completed, or other relevant instructions
complete their executions.

Off

- - R NO Off

M1031* Clear all non-latched areas

Off

- - R/W NO Off

M1032* Clear all latched areas

Off

- - R/W NO Off

M1033* Memory latched when STOP

Off

- - R/W NO Off

M1034* Disabling

all

Y

outputs

Off

- - R/W NO Off

M1035*

Enabling input point X as the RUN/STOP switch,
corresponding to D1035

(SA designates X7 only; SX designates X3 only; SC
designates X5 only)

- - - R/W YES Off

EH2/SV: the 3

rd

group pulse output CH2 (Y4, Y5) is

completed. (Not available in EH)

Off

- - R NO Off

M1036

SPD instruction is able to use X0 ~ X5 to detect the
flag (only available in SC_V1.4 and above)

Off

Off

- R/W NO Off

M1037

EH2/SV: the 4

th

group pulse output CH3 (Y6, Y7) is

completed. (Not available in EH)

Off

- - R NO Off

M1039* Fixing time scan mode

Off

- - R/W NO Off

M1040 Disabling

step

Off

- - R/W NO Off

M1041 Starting

step

Off

- Off R/W NO Off

M1042 Enabling

pulses

Off

- - R/W NO Off

M1043

Zero return completed

Off

- Off R/W NO Off

M1044

Zero point condition

Off

- Off R/W NO Off

M1045

Diabling all output reset

Off

- - R/W NO Off

M1046

Setting STL status as On

Off

- - R NO Off

M1047

Enabling STL monitoring

Off

- - R/W NO Off

M1048 Alarm

status

Off

- - R NO Off

M1049

Setting up alarm monitoring

Off

- - R/W NO Off

M1050 Inhibiting

I001

Off

- - R/W NO Off

M1051 Inhibiting

I101

Off

- - R/W NO Off

M1052 Inhibiting

I201

Off

- - R/W NO Off

M1053 Inhibiting

I301

Off

- - R/W NO Off

M1054 Inhibiting

I401

Off

- - R/W NO Off

M1055 Inhibiting

I501

Off

- - R/W NO Off