2 functions of devices in dvp-plc – Delta Electronics Programmable Logic Controller DVP-PLC User Manual
Page 51
![background image](/manuals/75807/51/background.png)
2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-23
1
(Normal
frequency)
A
B
2
(Double
frequency)
A
B
3
(Triple
frequency)
A
B
2-phase
2 inputs
4
(4 times
frequency)
A
B
5. Special registers for relevant flags and settings of high speed counters:
Flag
Function
M1150
DHSZ instruction in multiple set values comparison mode
M1151
The execution of DHSZ multiple set values comparison mode is completed.
M1152
Set DHSZ instruction as frequency control mode
M1153
DHSZ frequency control mode has been executed.
M1235 ~ M1244
Designating the counting direction of high speed counters C235 ~ C245
When M12□□ = Off, C2□□ will perform a counting up.
When M12□□ = On, C2□□ will perform a counting down.
M1245~ M1255
Designating the counting direction of high speed counters C246 ~ C255
When M12□□ = Off, C2□□ will perform a counting up.
When M12□□ = On, C2□□ will perform a counting down.
M1160
X5 as the reset input signal of all high speed counters
M1261
High-speed comparison flag for DHSCR instruction
M1264
Disable the external control signal input point of HHSC0 reset signal point (R)
M1265
Disable the external control signal input point of HHSC0 start signal point (S)
M1266
Disable the external control signal input point of HHSC1 reset signal point (R)
M1267
Disable the external control signal input point of HHSC1 start signal point (S)
M1268
Disable the external control signal input point of HHSC2 reset signal point (R)
M1269
Disable the external control signal input point of HHSC2 start signal point (S)
M1270
Disable the external control signal input point of HHSC3 reset signal point (R)
M1271
Disable the external control signal input point of HHSC3 start signal point (S)
M1272
Internal control signal input point of HHSC0 reset signal point (R)
M1273
Internal control signal input point of HHSC0 start signal point (S)
M1274
Internal control signal input point of HHSC1 reset signal point (R)
M1275
Internal control signal input point of HHSC1 start signal point (S)
M1276
Internal control signal input point of HHSC2 reset signal point (R)
M1277
Internal control signal input point of HHSC2 start signal point (S)
M1278
Internal control signal input point of HHSC3 reset signal point (R)
M1279
Internal control signal input point of HHSC3 start signal point (S)
M1289
High speed counter I010 interruption forbidden