2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-105

b) After enabling MODEM (M1184 = On), PLC has to initialize MODEM first (M1185 = On). If PLC fails to

initialize MODEM, the auto-answering function of the MODEM will not be enabled.

c) After MODEM is initialized, it will enter auto-answering mode automatically.

d) If the remote PC is disconnected, MODEM will enter stand-by mode automatically and if the user turns off

MODEM now, MODEM will have to be initialized again when it is turned on again.

e) The connection speed is set by PLC as 9,600bps fixed and modification on the speed is not allowed.

MODEM has to be able to support the speed of 9,600bps and above.

f) The initialization format from PLC to MODEM are ATZ and ATS0 = 1.

g) If PLC fails to initialize MODEM, use the super terminal in PC to initialize it by the format ATZ and ATS0 = 1.

Function Group

Latched Area

Number

D1200 ~ D1219

Contents:

1.

The latched area for EH/EH2/SV/SA/SX/SC is from the start address No. to the end address No.

2.

See the tables in Chapter 2.1 for more details.

Function Group

Force On/Off of Input Point X

Number

M1304

Contents:

1.

For SA/SX/SC, when M1304 = On, peripheral devices, e.g. WPLSoft or HPP, can force On/Off of X0 ~ X17, but

the hardware LED will not respond to it.

2.

For EH/EH2/SV, when M1304 = On, peripheral devices, e.g. WPLSoft or HPP, can force On/Off of input point X,

and the hardware LED will respond to it.

Function Group

High-speed Output Pulse Stop Mode

Number

M1310 ~ M1311, M1334 ~ M1335, D1166 ~ D1167, D1343 ~ D1353

Contents:

1. Special D and special M for high-speed pulse output stop mode: (SC_V1.4 and versions above are with an

additional mode 3)

Device No.

Function

M1334

Select stop mode for Y10 pulse

M1335

Select stop mode for Y11 pulse

M1310

Immediately stop Y10 pulse output

M1311

Immediately stop Y11 pulse output

D1166

X10 rising-edge/falling-edge counting mode switch

D1167

X11 rising-edge/falling-edge counting mode switch

D1343 Acceleration/deceleration

time for Y10 pulse output

D1353

Acceleration/deceleration time for Y11 pulse output

2. How do Y10 pulse output stop modes work: