2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-86
K500
MOV
M1002
D1104
K1000
MOV
D500
K100
MOV
D501
MOV
D502
K80000
DMOV
D503
K10000
DMOV
D505
K10000
M1115
SET
D500 ~ D506 as parameter addresses
Start frequency: 1KHz
Interval frequency: 100Hz
Target frequency: 10KHz
Number of output pulses: 80,000
Number of pulses in accel/decel section: 10,000
a) When PLC is in RUN status, store all parameter settings into the registers designated in D1104.
b) When M1115 = On, the acceleration/deceleration pulse output will start.
c) M1116 = On in the acceleration process. When the speed reaches its target, M1117 will be On. M1118 = On
in the deceleration process. When the speed reaches its target, M1119 will be On.
d) M1115 will not be reset automatically. You have to check the conditions during the process and reset it.
e) Pulse output curves:
10K
1K
10,000
70,000
80,000
Frequency (Hz)
Number
of pulses
10K
1K
2,606
8,606
11,213
Frequency (Hz)
Time (ms)
Function Group
Special High-Speed Pulse Output
Number
M1133 ~ M1135, D1133
Contents:
1.
Special D and special M for special high-speed pulse Y0 (50KHz)for SA/SX/SC (not applicable to SC_V1.4 and
versions above):