2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-86

K500

MOV

M1002

D1104

K1000

MOV

D500

K100

MOV

D501

MOV

D502

K80000

DMOV

D503

K10000

DMOV

D505

K10000

M1115

SET

D500 ~ D506 as parameter addresses

Start frequency: 1KHz

Interval frequency: 100Hz

Target frequency: 10KHz

Number of output pulses: 80,000

Number of pulses in accel/decel section: 10,000

a) When PLC is in RUN status, store all parameter settings into the registers designated in D1104.

b) When M1115 = On, the acceleration/deceleration pulse output will start.

c) M1116 = On in the acceleration process. When the speed reaches its target, M1117 will be On. M1118 = On

in the deceleration process. When the speed reaches its target, M1119 will be On.

d) M1115 will not be reset automatically. You have to check the conditions during the process and reset it.

e) Pulse output curves:

10K

1K

10,000

70,000

80,000

Frequency (Hz)

Number

of pulses

10K

1K

2,606

8,606

11,213

Frequency (Hz)

Time (ms)