8 Application Instructions API 100-149

DVP-PLC Application Manual

8-53

API Mnemonic

Operands

Function

137

D COSH P

Hyperbolic Cosine

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word devices

Program Steps

Type

OP

X Y M S K H

KnX KnY KnM KnS T

C

D

E

F

S

*

*

*

D

*

DCOSH, DCOSHP: 9 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

S

: Source value (binary floating point) D: COSH value

Explanations:

1. See the specifications of each model for their range of use.

2. Flags: M1020 (zero flag); M1021 (borrow flag); M1022 (carry flag)

3. COSH

value=(e

s

+e

-s

)/2. The result is stored in D.

Program Example:

1. When X0 = On, obtain the COSH value of binary floating point (D1, D0) and store the binary floating point result in

(D11, D10).

DCOSH

X0

D0

D10

D1

D0

D11

D10

COSH value

binary floating point

binary floating point

5. If the absolute value of the result > maximum floating point available, the carry flag M1022 = On.

6. If the absolute value of the result < minimum floating point available, the borrow flag M1021 = On.

7. If the result = 0, the zero flag M1020 = On.

Remarks:

For floating point operations, see “5.3 Handling of Numeric Values”.