8 Application Instructions API 100-149

DVP-PLC Application Manual

8-14

API Mnemonic

Operands

Function

105

RDST

Read VFD-A Status

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T

C

D

E

F

S

*

*

*

n

*

*

*

RDST: 5 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

S

: Address of communicatino device n: Target to be instructed

Explanations:

1. Range

of

S

: K0 ~ K31

2. Range

of

n

: K0 ~ K3

3. See the specifications of each model for their range of use.

4. ES series MPU does not support E, F index register modification.

5. Flags: See API 80 RS for explanations on M1120 ~ M1131, M1140 ~ M1143
6. n: Instructed target (to be read) in AC motor drive

n=0, frequency
n=1, output

frequency

n=2, output

current

n=3, running

instruction

7. Data sent back (feedback) from AC motor drive (11 bytes, see VFD-A user manual) are stored in the low bytes

of D1070 ~ D1080.

”Q, S, B, Uu, Nn, ABCD”

Feedback

Explanation Data

storage

Q

Start word: ’Q’ (51H).

D1070 low

S

Checksum code: 03H.

D0171 low

B

Instruction authorization. correct: 06H, incorrect: 07H.

D1072 low

U

D1073 low

U

Communication address (address: 00~31). ”Uu” = (“00” ~ ”31”) indicated
in ASCII format.

D1074 low

N

D1075 low

N

Instructed target (00 ~ 03).”Nn” = (“00 ~ 03”) indicated in ASCII format.

D1076 low

A

D1077 low

B

D1078 low

C

D1079 low

D

Instructed data. The content of ”ABCD” differs upon the instructed targets
(00 ~ 03). 00 ~ 03 indicate frequency, current and running mode
respectively. Please refer to the explanations below for details.

D1080 low

Nn = “00”

Frequency instruction = ABC.D (Hz)

Nn = “01”

Output instruction = ABC.D (Hz)

Nn = “02”

Output current = ABC.D (A)

PLC will automatically convert the ASCII characters of ”ABCD” into numerals and store the
numeral in D1050. For example, assume ”ABCD” = “0600”, PLC will convert ABCD into K0600
(0258 H) and store it in the special register D1050.