2 functions of devices in dvp-plc – Delta Electronics Programmable Logic Controller DVP-PLC User Manual
Page 104
![background image](/manuals/75807/104/background.png)
2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-76
Device No.
Cleared Device
M1032
Contact status of M and S for latched
Contact and timing coil of accumulative timer T
Contac and timing coil of high-speed counter C for latched
Present value register of D for latched
Present value register of accumulative timer T
Present value register of high-speed counter C for latched
Function Group
Output Latched During STOP
Number
M1033
Contents:
When M1033 = On and PLC goes from “RUN” to “STOP”, the On/Off status of output will be ratained.
Assume the output contact load of the PLC is a heater, when PLC switches from RUN to STOP, the status of the
heater will be retained. After the PLC program is modified, the PLC will RUN again.
Function Group
All Output Y Inhibited
Number
M1034
Contents:
When M1034 = On, all Y outputs will turn “Off”.
M1034
all outputs inhibited
Function Group
RUN/STOP Switch
Number
M1035, D1035
Contents:
1.
When M1035 = On, EH/EH2/SV series MPU will determine the content (K0 ~ K15) in D1035 to enable input
points X0 ~ X17 as the RUN/STOP switch.
2.
When M1035 = On, SA/SX/SC series MPU will enable the input point X7 (in SA), X3 (in SX) and X5 (in SC) as
the RUN/STOP switch.
Function Group
Detecting Speed of X0 ~ X5
Number
M1036
Contents:
1. For SC_V1.4 and above, SPD can detect the speed of X0 ~ X5 at the same time. The total bandwidth is 40KHz.
2. Program
example: