2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-76

Device No.

Cleared Device

M1032

Contact status of M and S for latched

Contact and timing coil of accumulative timer T

Contac and timing coil of high-speed counter C for latched

Present value register of D for latched

Present value register of accumulative timer T

Present value register of high-speed counter C for latched

Function Group

Output Latched During STOP

Number

M1033

Contents:

When M1033 = On and PLC goes from “RUN” to “STOP”, the On/Off status of output will be ratained.

Assume the output contact load of the PLC is a heater, when PLC switches from RUN to STOP, the status of the

heater will be retained. After the PLC program is modified, the PLC will RUN again.

Function Group

All Output Y Inhibited

Number

M1034

Contents:

When M1034 = On, all Y outputs will turn “Off”.

M1034

all outputs inhibited

Function Group

RUN/STOP Switch

Number

M1035, D1035

Contents:

1.

When M1035 = On, EH/EH2/SV series MPU will determine the content (K0 ~ K15) in D1035 to enable input

points X0 ~ X17 as the RUN/STOP switch.

2.

When M1035 = On, SA/SX/SC series MPU will enable the input point X7 (in SA), X3 (in SX) and X5 (in SC) as

the RUN/STOP switch.

Function Group

Detecting Speed of X0 ~ X5

Number

M1036

Contents:

1. For SC_V1.4 and above, SPD can detect the speed of X0 ~ X5 at the same time. The total bandwidth is 40KHz.

2. Program

example: