7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7-67

API Mnemonic

Operands

Function

74

SEGL

Seven Segment with Latch

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX KnY KnM KnS T

C

D

E

F

S

*

*

*

*

*

*

*

*

*

*

*

D

*

n

*

*

SEGL: 7 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

S

: Source device to be displayed in 7-segment display D: Start device for 7-segment display scan output

n

: Polarity setting of output signal and scan signal

Explanations:

1. Range

of

n

: 0 ~ 7. See remarks for more details.

2. For ES series MPU, the instruction can only be used once in the program. For EH series MPU, the instruction

can be used twice in the program. For SA series MPU, there is no limitation on the times of using the instruction,

but only one instruction can be executed at a time.

3. For ES/EX/SS/SA/SX/SC series MPU, the last digit of D should be 0 and it does not support E, F index register

modification.

4. Flag: M1029 (SEGL execution completed)

5. This instruction occupies 8 or 12 continuous external input points starting from D for displaying 1 or 2 4-digit

7-segment display data and outputs of scanned signals. Every digit carries a 7-segment display drive (to convert

the BCD codes into 7-segment display signal). The drive also carries latch control signals to retain the

7-segment display.

6. n decides there be 1 group or 2 groups of 4-digit 7-segment display and designates the polarity for the output.

7. When there is 1 group of 4-digit output, 8 output points will be occupied. When there are 2 groups of 4-digit

output, 12 output points will be occupied.

8. When this instruction is being executed, the scan output terminals will circulate the scan in sequence. When the

drive contact of the instruction goes from Off to On again, the scan output terminal will restart the scan again.

Program Example:

1. When X10 = On, this instruction starts to be executed, Y10 ~ Y17 construct a 7-segment display scan circuit.

The value in D10 will be converted into BCD codes and sent to the first group 7-segment display. The value in

D11 will be converted into BCD codes as well and sent to the second group 7-segment display. If the values in

D10 and D11 exceed 9,999, operational error will occur.

X10

SEGL

D10

Y10

K4

2. When X10 = On, Y14 ~ Y17 will circulate the scan automatically. Every cycle requires 12 scan period. Whenever

a cycle is completed, M1029 will be On for a scan period.