beautypg.com

Delta Electronics Programmable Logic Controller DVP-PLC User Manual

Page 288

background image

7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7-4

2.

The figure below illustrates the external wiring of the 2-array matrix input loop constructed by X40 ~ X47 and

Y40 ~ Y41. The 16 switches correponds to the internal relays M10 ~ M17, M20 ~ M27. Should be used with

MTR instruction.

S/S

X40

X41 X42

X43

X44 X45

X47

X46

C

Y40

Y41 Y42

Y43

Y44 Y45

Y47

Y46

M1 0

X 41

M20

M11

M12

M1 3

M1 4

M15

M1 6

M1 7

X42

X43

X44

X 45

X46

X47

M2 1

M2 2

M2 3

M2 4

M25

M2 6

M2 7

+24V

24G

M10: the internal relay
corresponding to

the external switch

Must c onnec t to the diode
of 0.1A/50V, 1N4148, in series

3.

See the figure above. The 8 points starting from X40 start to perform a matrix scan from Y40 ~ Y41 (n = 2). D

2

designates that the start device No. of the read results is M10, indicating that the first array is read to M10 ~

M17 and the second array is read to M20 ~ M27.

2

4

Y41

Y40

25ms

1

3

Read input signals in the 1st array

Read input signals in the 2nd array

Processing time of each array: approx. 25ms