5 Categories & Use of Application Instructions

DVP-PLC Application Manual

5-7

The application instructions for DVP-PLC are represented as API 00 ~ API 246. Every application instruction

has its own mnemonic. For example, the mnemonic of API 12 is MOV. If you are using the ladder diagram editing

software (WPLSoft) to input API 12 into the program, you only have to enter “MOV”. If you are using the handheld

programming panel (HPP) to input API 12 into the program, you will have to enter the API No. “12”.

Different application instructions designate different operands. Take MOV instruction for example:

X0

MOV

K10

D10

Instruction
mnemonic

Operands

MOV instruction is to move the operand designated in S to the operand designated in

D

.

S

Source operand: If there are more than 1 source operands, they will be represented as S

1

, S

2

, ….

D

Destination operand: If there are more than 1 destination operands, they will be represented as

D

1

, D

2

, ….

If the operand can only be constant K/H or a register, it will be represented as m, m

1

, m

2

, n, n

1

, n

2

, ….

ƒ

Length of operand (16-bit instruction or 32-bit instruction)

Depending on the contents in the operand, the length of an operand can be 16-bit or 32-bit. Therefore, a

16-bit instruction is for processing 16-bit operands, and 32-bit instruction is for processing 32-bit operands. The

32-bit instruction is indicated by adding a “D” before the 16-bit instruction.

16-bit MOV instruction

X0

K10

D10

MOV

When X0 = On, K10 will be sent to D10.

32-bit DMOV instruction

X1

D10

D20

DMOV

When X1 = On, the content in (D11, D10) will be sent

to (D21, D20).

ƒ

Continuous execution instruction and pulse execution instruction

Continuous execution and pulse execution are the two types of execution for an application instruction. Due to

that the execution time required will be shorter when the instruction is not executer, the pulse execution

instructions are used more to shorten the scan period. Instructions marked with a “P" following the mnemonic are

pulse execution instruction. Some instructions are mostly used as pulse execution type, e.g. INC, DEC, the kind of

displacement instructions.