7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7-78

CR#24.

FROM/TO Application Example 2:

Adjust the A/D conversion curve of DVP-04AD. Set the OFFSET value of CH2 as 2mA (= K400

LSB

) and GAIN value

as 18mA (= K3,600

LSB

).

M1002

TO

K0

K1

H18

K1

TO

K0

K33

H0

K1

X0

TO

K0

K19

K400

K1

TO

K0

K25

K3600

K1

1. Write H18 to CR#1 of anlog input module No. 0 and set CH2 as mode 3 (current input: -20mA ~ +20mA).

2. Write H0 to CR#33 and allow OFFSET/GAIN tuning in CH1 ~ CH4.

3. When X0 goes from Off to On, write the OFFSET value K400

LSB

into CR#19 and the GAIN value K3,600

LSB

into

CR#25.

FROM/TO Application Example 3:

Adjust the D/A conversion curve of DVP-02DA. Set the OFFSET value of CH2 as 0mA (= K0

LSB

) and GAIN value as

10mA (= K1,000

LSB

).

M1002

TO

K1

K1

H18

K1

TO

K1

K33

H0

K1

X0

TO

K1

K22

K0

K1

TO

K1

K28

K1000

K1

1. Write H18 to CR#1 of anlog output module No. 1 and set CH2 as mode 3 (current output: 0mA ~ +20mA).

2. Write H0 to CR#33 and allow OFFSET/GAIN tuning in CH1 and CH2.

3. When X0 goes from Off to On, write the OFFSET value K0

LSB

into CR#22 and the GAIN value K1,000

LSB

into

CR#28.

FROM/TO Application Example 4:

Adjust the D/A conversion curve of DVP-02DA. Set the OFFSET value of CH2 as 2mA (= K400

LSB

) and GAIN value

as 18mA (= K3,600

LSB

).

1. Write H10 to CR#1 of anlog output module No. 1 and set CH2 as mode 2 (current output: +4mA ~ +20mA).

2. Write H0 to CR#33 and allow OFFSET/GAIN tuning in CH1 and CH2.

3. When X0 goes from Off to On, write the OFFSET value K400

LSB

into CR#23 and the GAIN value K3,600

LSB

into

CR#29.