7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7-27

7.

EH series MPU has two groups of A-B phase pulse output from CH0 (Y0, Y1) and CH1 (Y2, Y3); EH2/SV series

MPU has four groups of A-B phase pulse output from CH0 (Y0, Y1), CH1 (Y2, Y3), CH2 (Y4, Y5) and CH3 (Y6,

Y7). See 2.3 and remarks for how to set up.

8.

When PLSY instruction is executed, it will designate the number of output pulses (S

2

) output from the output

device (D) at a pulse output frequency (S

1

).

9.

When PLSY instruction is used in the program, its outputs cannot be the same as those in API 58 PWM and API

59 PLSR.

10. Pulse output completed flags for all series:

MPU

ES/EX/SS
SA/SX/SC

SC

EH/EH2/SV

EH2/SV

Output device

Y0

Y1

Y10

Y11

Y0

Y2

Y4

Y6

Flag

M1029 M1030 M1102 M1103 M1029 M1030 M1036 M1037

11. For ES/EX/SS/SA/SX/SC/EH series MPU, when PLSY and DPLSY instruction is disabled, the pulse output

completed flags will all be Off automatically.

12. For EH2/SV series MPU, when PLSY and DPLSY instruction is disabled, the user will have to reset the pulse

output completed flags.

13. The user has to reset the pulse output completed flags after the pulse output is completed.

14. After PLSY instruction starts to be executed, Y will start a pulse output. Modifying S

2

at this moment will not

affect the current output. If you wish to modify the number of output pulses, you have to first stop the execution

of PLSY instruction and modify the number.

15. S

1

can be modified when the program executes to PLSY instruction.

16. Off time : On time of the pulse output = 1 : 1.

17. When the program executes to PLSY instruction, the current number of output pulses will be stored in the

special data registers D1336 ~ D1339. See remarks for more details.

18. For SA/EH series MPU, there is no limitation on the times using this instruction. For SA/SX/SC/EH series MPU,

the program allows two instructions being executed at the same time. For EH2/SV series MPU, the program

allows four instructions being executed at the same time.

Program Example:

1.

When X0 = On, there will be 200 pulses output from Y0 at 1KHz. When the pulse output is completed, M1029

will be On and Y10 will be On.

2.

When X0 = Off, the pulse output from Y0 will stop immediately. When X0 is On again, the output will start again

ffrom the first pulse.

X0

PLSY

K1000

K200

Y0

M1029

Y10