5 Categories & Use of Application Instructions

DVP-PLC Application Manual

5-14

ƒ

The decimal floating point can be used in the following instructions:

D EBCD: Converting binary floating point to decimal floating point

D EBIN: Converting decimal floating point to binary floating point

ƒ

Zero flag (M1020), carry flag (M1021), carry flag (M1022) and the floating point operation instructions:

Zero flag: M1020 = On if the operational result is “0”.

Borrow flag: M1021 = On if the operational result exceeds the minimum unit.

Carry flag: M1022 = On if the absolute value of the operational result exceeds the range of use.

5.4 E, F Index Register Modification

The index registers are 16-it registers. There are 2 points of E, F in ES/EX/SS, 8 points E0 ~ E3 and F0 ~ F3 in

SA/SX/SC, and 16 points E0 ~ E7 and F0 ~ F7 in EH/EH2/SV series MPU.

F0

E0

E0

F0

16-bit

16-bit

32-bit

High byte

Low byte

ƒ

E and F index registers are 16-bit data registers, can be read and

written.

ƒ

If you need a 32-bit register, you have to designate E. In this case, F

will be covered up by E and cannot be used; otherwise, the contents

in E may become incorrect. (We recommend you use MOVP

instruction to reset the contents in D to 0 when the PLC is switched

on.)

ƒ

Combination of E and F when you designate a 32-bit index register:

(E0, F0), (E1, F1), (E2, F2), ... (E7, F7)

MOV K20E0 D10F0

E0 = 8 F0 = 14
20 + 8 = 28 10 + 14 = 24
Transmission K28 D24

See the diagram in the left hand side. E, F index register

modification refers to the content in the operand changes with

the contents in E and F.

For example, E0 = 8 and K20E0 represents constant K28 (20

+ 8). When the condition is true, constant K28 will be

transmitted to register D24.

Devices modifiable in ES/EX/SS series MPU: P, X, Y, M, S, KnX, KnY, KnM, KnS, T, C, D.

Devices modifiable in SA/SX/SC series MPU: P, X, Y, M, S, KnX, KnY, KnM, KnS, T, C, D

Devices modifiable in EH/EH2/SV series MPU: P, I, X, Y, M, S, K, H, KnX, KnY, KnM, KnS, T, C, D

E and F can modify the devices listed above but cannot modify themselves and Kn. K4M0E0 is valid and

K0E0M0 is invalid. Grey columns in the table of operand at the beginning page of each application instruction indicate

the operands modifiable by E and F.