beautypg.com

2 functions of devices in dvp-plc – Delta Electronics Programmable Logic Controller DVP-PLC User Manual

Page 134

background image

2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-106

a) Using Y10 pulse output

Mode 1 – Planned deceleration

Applicable to: DDRVI and DDRVA instructions

Criteria for executing planned deceleration: Shut down the criteria contact for pulse output instruction and

turn “Off” M1334.

The time from executing planned deceleration to the end of pulse output: The time set in D1343 (for

acceleration/deceleration)

The solid lines in the figure below are the originally planned routes and the dotted lines refer to the routes

after planned deceleration is executed.

Frequency

Target frequency

Start frequency

D1340

Instruction shut down and M1334 = Off

Time

Acceleration/deceleration time

D1343

Mode 2 – Output shutdown

Applicable to: DDRVI, DDRVA, PLSY instructions

Criteria for executing output shutdown: Shut down the criteria contact for pulse output instruction and turn

“On” M1334.(Because PLSY does not have acceleration/deceleration setting, M1334 does not need to

be set in PLSY)

The time from executing output shutdown to the end of pulse output: Max. 1 scan cycle.

The solid lines in the figure below are the originally planned routes and the dotted lines refer to the routes

after output shutdown is executed.

Frequency

Target frequency

Start frequency

D1340

Instruction shut down and M1334 = On

Time

Mode 3 – Immediate output shutdown

Applicable to: DDRVI, DDRVA, PLSY instructions

Criteria for executing immediate output shutdown: M1310 = On (set before executing the instruction) and

the criteria triggers set in X10 (D1166 = K0 refers to rising-edge; D1166 = K1 refers to falling-edge)

The time from executing immediate output shutdown to the end of pulse output: Max. 1 pulse time.

The solid lines in the figure below are the originally planned routes and the dotted lines refer to the

routes after X10 is triggered.