7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7-28

1

2

3

200

0.5ms

1ms

Y0 output

Remarks:

1. Flags and special registers for ES/EX/SS series MPU:

M1010: When On, Y0 output will be continuous with no limitation on the number of pulses. When Off, the

number of output pulses from Y0 will be decided by S

2

.

M1023: When On, Y1 output will be continuous with no limitation on the number of pulses. When Off, the

number of output pulses from Y1 will be decided by S

2

.

M1029: On when Y0 pulse output is completed.

M1030: On when Y1 pulse output is completed.

M1078: Y0 output pauses.

M1079: Y1 output pauses.

D1030: Low word of the current number of output pulses from Y0

D1031: High word of the current number of output pulses from Y0

D1032: Low word of the current number of output pulses from Y1

D1033: High word of the current number of output pulses from Y1

2. Flags and special registers for SA/SX/SC series MPU:

M1010: (SA/SX/SC) When On, Y0 output will be continuous with no limitation on the number of pulses.

When Off, the number of output pulses from Y0 will be decided by S

2

.

M1023: (SA/SX/SC) When On, Y1 output will be continuous with no limitation on the number of pulses.

When Off, the number of output pulses from Y1 will be decided by S

2

.

M1029: (SA/SX/SC) On when Y0 pulse output is completed.

M1030: (SA/SX/SC) On when Y1 pulse output is completed.

M1078: (SA/SX/SC) Y0 output pauses.

M1079: (SA/SX/SC) Y1 output pauses.

M1102: (SC) On when Y10 pulse output is completed.

M1103: (SC) On when Y11 pulse output is completed.

D1030: (SA/SX/SC) Low word of the current number of output pulses from Y0

D1031: (SA/SX/SC) High word of the current number of output pulses from Y0

D1032: (SA/SX/SC) Low word of the current number of output pulses from Y1

D1033: (SA/SX/SC) High word of the current number of output pulses from Y1

D1348: (SC) Low word of the current number of output pulses from Y10

D1349: (SC) High word of the current number of output pulses from Y10

D1350: (SC) Low word of the current number of output pulses from Y11

D1351: (SC) High word of the current number of output pulses from Y11