Delta Electronics Programmable Logic Controller DVP-PLC User Manual
Page 312
![background image](/manuals/75807/312/background.png)
7 Application Instructions API 50-99
D V P - P L C A P P L I C AT I O N M A N U A L
7-28
1
2
3
200
0.5ms
1ms
Y0 output
Remarks:
1. Flags and special registers for ES/EX/SS series MPU:
M1010: When On, Y0 output will be continuous with no limitation on the number of pulses. When Off, the
number of output pulses from Y0 will be decided by S
2
.
M1023: When On, Y1 output will be continuous with no limitation on the number of pulses. When Off, the
number of output pulses from Y1 will be decided by S
2
.
M1029: On when Y0 pulse output is completed.
M1030: On when Y1 pulse output is completed.
M1078: Y0 output pauses.
M1079: Y1 output pauses.
D1030: Low word of the current number of output pulses from Y0
D1031: High word of the current number of output pulses from Y0
D1032: Low word of the current number of output pulses from Y1
D1033: High word of the current number of output pulses from Y1
2. Flags and special registers for SA/SX/SC series MPU:
M1010: (SA/SX/SC) When On, Y0 output will be continuous with no limitation on the number of pulses.
When Off, the number of output pulses from Y0 will be decided by S
2
.
M1023: (SA/SX/SC) When On, Y1 output will be continuous with no limitation on the number of pulses.
When Off, the number of output pulses from Y1 will be decided by S
2
.
M1029: (SA/SX/SC) On when Y0 pulse output is completed.
M1030: (SA/SX/SC) On when Y1 pulse output is completed.
M1078: (SA/SX/SC) Y0 output pauses.
M1079: (SA/SX/SC) Y1 output pauses.
M1102: (SC) On when Y10 pulse output is completed.
M1103: (SC) On when Y11 pulse output is completed.
D1030: (SA/SX/SC) Low word of the current number of output pulses from Y0
D1031: (SA/SX/SC) High word of the current number of output pulses from Y0
D1032: (SA/SX/SC) Low word of the current number of output pulses from Y1
D1033: (SA/SX/SC) High word of the current number of output pulses from Y1
D1348: (SC) Low word of the current number of output pulses from Y10
D1349: (SC) High word of the current number of output pulses from Y10
D1350: (SC) Low word of the current number of output pulses from Y11
D1351: (SC) High word of the current number of output pulses from Y11