6 Application Instructions API 00-49

DVP-PLC Application Manual

6-63

API Mnemonic

Operands

Function

43

D SUM P

Sum of Active Bits

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T C D E F

S

* *

*

*

*

*

*

*

*

*

*

D

*

*

*

*

*

*

*

*

SUM, SUMP: 5 steps

DSUM, DSUMP: 9 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

S

: Source device D: Destination device for storing counted value

Explanations:

1. If

S

and D are used in device F, only 16-bit instruction is applicable.

2.

See the specifications of each model for their range of use.

3.

Flag: M1020 (zero flag)

4.

Among the bits of S, the total of bits whose content is “1” will be stored in D.

5.

When all the 16 bits of S are “0”, zero flag M1020 = On.

6.

When 32- instruction is in use, D will occupy 2 registers.

Program Example:

When X10 = On, among the 16 bits of D0, the total of bits whose content is “1” will be stored in D2.

X10

SUM

D0

D2

0

0

0

0

0

0

0

1

1

1

0

0

0

0

0

0

K3

D2

D0