8 Application Instructions API 100-149

DVP-PLC Application Manual

8-17

API Mnemonic

Operands

Function

107

LRC P

Checksum LRC Mode

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX KnY KnM KnS T

C

D

E

F

S

*

n

*

*

*

D

*

LRC, LRCP: 7 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

S

:

Start operation device for ASCII mode checksum n: Number of calculated bits D: Start device for storing the

operation result LRC checksum: See remarks.

Explanations:

1. Range

of n: K1 ~ K256

2. See the specifications of each model for their range of use.

3. Flag: M1161 (switching between 8/16 bit modes)

4. n has to be even. If n does not fall within its range, an operation error will occur, the instruction will not be

executed, M1067, M1068 = On and D1067 will record the error code H’0E1A.

5. In 16-bit conversion mode: When M1161 = Off, S divides its hex data area into higher 8 bits and lower 8 bits

and performs LRC checksum operation on each bit. The data will be sent to the higher 8 bits and lower 8 bits in

D

. n = the number of calculated bits.

6. In 8-bit conversion mode: When M1161 = On, S divides its hex data area into higher 8 bits (invalid data) and

lower 8 bits and performs LRC checksum operation on each bit. The data will be sent to the lower 8 bits in D

and occupy 2 registers. n = the number of calculated bits. (All higher bits in D are “0”.)

Program Example:

When PLC communicates with VFD-S series AC motor drives (In ASCII mode, M1143 = Off), (In 8-bit mode, M1161 =

On), the sent data write in advance the 6 data read starting from H2101 of VFD-S.

MOV

D1120

H86

M1002

SET

M1120

SET

M1122

MOV

D1129

K100

X10

M1123

RST

M1123

RS

D100

K17

D120

K35

pulse

receiving completed

Process of receiving data

Set up communication protocol to 9600, 7, E, 1

Retain communication protocol

Set up communication time-out: 100ms

Set up transmission request

Sending/receiving of data is completed.
The flag is reset.

Write in sent data in advance

sending request pulse