2 Functions of Devices in DVP-PLC
DVP-PLC Application Manual
2-107
X10 triggered
Frequency
Target frequency
Start frequency
D1340
Time
Max. Stop time = 1 pulse time
b) Using Y11 pulse output
Mode 1 – Planned deceleration
Applicable to: DDRVI and DDRVA instructions
Criteria for executing planned deceleration: Shut down the criteria contact for pulse output instruction and
turn “Off” M1335.
The time from executing planned deceleration to the end of pulse output: The time set in D1353 (for
acceleration/deceleration)
Mode 2 – Output shutdown
Applicable to: DDRVI, DDRVA, PLSY instructions
Criteria for executing output shutdown: Shut down the criteria contact for pulse output instruction and turn
“On” M1335. (Because PLSY does not have acceleration/deceleration setting, M1335 does not need to be
set in PLSY)
The time from executing output shutdown to the end of pulse output: Max. 1 scan cycle.
Mode 3 – Immediate output shutdown
Applicable to: DDRVI, DDRVA, PLSY instructions
Criteria for executing immediate output shutdown: M1311 = On (set before executing the instruction) and
the criteria triggers set in X11 (D1167 = K0 refers to rising-edge; D1167 = K1 refers to falling-edge)
The time from executing immediate output shutdown to the end of pulse output: Max. 1 pulse time.
3. Note:
a) The execution criteria M1334 and M1335 for mode 1 and 2 have to be set before executing pulse output
shutdown instruction. The execution criteria M1310, M1311 and trigger criteria D1166, D1167 for mode 3
have to be set before the pulse output instruction is executed.
b) In mode 3 (immediate output shutdown), Y10 can only be used with X10 and Y11 with X11.
c) When using X10 or X11 in mode 3, DO NOT use X10 or X11 as the input high-speed counter.
Function Group
Right-Side Special Extension Module ID
Number
D1320 ~ D1327
Contents:
1.
The ID of special extension module, if any, connected to EH/EH2/SV are stored in D1320 ~ D1327 in sequence.
2.
Special extension module ID for EH:
Module Name
Module ID
(hex)
Module Name
Module ID
(hex)
DVP04AD-H H’0400 DVP01PU-H H’0110