2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-107

X10 triggered

Frequency

Target frequency

Start frequency

D1340

Time

Max. Stop time = 1 pulse time

b) Using Y11 pulse output

Mode 1 – Planned deceleration

Applicable to: DDRVI and DDRVA instructions

Criteria for executing planned deceleration: Shut down the criteria contact for pulse output instruction and

turn “Off” M1335.

The time from executing planned deceleration to the end of pulse output: The time set in D1353 (for

acceleration/deceleration)

Mode 2 – Output shutdown

Applicable to: DDRVI, DDRVA, PLSY instructions

Criteria for executing output shutdown: Shut down the criteria contact for pulse output instruction and turn

“On” M1335. (Because PLSY does not have acceleration/deceleration setting, M1335 does not need to be

set in PLSY)

The time from executing output shutdown to the end of pulse output: Max. 1 scan cycle.

Mode 3 – Immediate output shutdown

Applicable to: DDRVI, DDRVA, PLSY instructions

Criteria for executing immediate output shutdown: M1311 = On (set before executing the instruction) and

the criteria triggers set in X11 (D1167 = K0 refers to rising-edge; D1167 = K1 refers to falling-edge)

The time from executing immediate output shutdown to the end of pulse output: Max. 1 pulse time.

3. Note:

a) The execution criteria M1334 and M1335 for mode 1 and 2 have to be set before executing pulse output

shutdown instruction. The execution criteria M1310, M1311 and trigger criteria D1166, D1167 for mode 3

have to be set before the pulse output instruction is executed.

b) In mode 3 (immediate output shutdown), Y10 can only be used with X10 and Y11 with X11.

c) When using X10 or X11 in mode 3, DO NOT use X10 or X11 as the input high-speed counter.

Function Group

Right-Side Special Extension Module ID

Number

D1320 ~ D1327

Contents:

1.

The ID of special extension module, if any, connected to EH/EH2/SV are stored in D1320 ~ D1327 in sequence.

2.

Special extension module ID for EH:

Module Name

Module ID

(hex)

Module Name

Module ID

(hex)

DVP04AD-H H’0400 DVP01PU-H H’0110