2 Functions of Devices in DVP-PLC

DVP-PLC Application Manual

2-117

10. Auto mode and maual mode:

a) Auto mode (M1351 = On): Master PLC automatically reads/writes from/to Slave PLC and stops when

M1350/M1351 = Off to terminate EASY EASY PLC LINK.

b) Manual mode (M1352 = On): When M1352 = On, you also have to set up the times of polling in D1431. One

time of polling refers to the completion of reading and writing all Slaves. After the EASY PLC LINK is

enabled, D1432 will start to count how many LINKs have been done.

When D1431 = D1432, EASY EASY

PLC LINK stops and M1352 is reset. To re-enable EASY EASY PLC LINK in the manual mode, simply turn

“On” M1352 and D1431 will starts to count the times of LINK again.

c) Note:

i) Automatic mode (M1351) and manual mode (M1352) cannot be “On” at the same time; otherwise EASY

EASY PLC LINK will stop and M1350 will be reset.

ii) For EH/EH2/SV: M1350 has to be reset before switching between automatic mode and manual mode. For

SA/SX/SC: No such restriction

iii) The communication timeout is adjustable (D1129, range: 200 ≤ D1129 ≤ 3,000). If D1129 falls out the range,

PLC will determine the time by 200 or 3,000. The timeout setting of EASY EASY PLC LINK is only valid if it is

set before the LINK is enabled. If the number of read/written data >16, the communication timeout shall be >

500ms in case a communication timeout may occur.

iv) EASY EASY PLC LINK is only workable when the baud rate is > 1,200bps. If the baud rate is < 9,600, the

communication timeout setting shall be > 1 second.

v) The communication is unworkable when the number of read/written data = 0.

vi) EASY EASY PLC LINK does not support the reading/writing from/to 32-bit counters (C200 ~ C255).

vii) The maximum set value for D1399 is 230. If the set value is bigger than 230, PLC will automatically correct it

as 230. The minimum set value for D1300 is 1. If the set value is smaller than 1, PLC will automatically

correct it as 1.

viii) Setting up of D1399 has to be done before EASY EASY PLC LINK is enabled. After EASY EASY PLC LINK

is enabled, setting up D1399 will not result in any changes.

ix) Advantages (when using a multi-layer network): Assume you are using a network with 3 layers and the first

and second layer and the second and third layer are using EASY EASY PLC LINK for communication, the

IDs in the second and third layer will definitely overlap due to the old version of EASY PLC LINK detects only

Slave ID#1 ~ 16. When the IDs of Slave and Master overlap, EASY PLC LINK will ignore the PLC of

overlapping ID, resulting in the situation that the third layer can have only 15 PLCs. Therefore, D1399 allows

more PLCs connected in a multi-layer network.