f) Special registers for relevant flags and settings of high speed counters:

Flag

Function

M1150

DHSZ instruction in multiple set values comparison mode

M1151

The execution of DHSZ multiple set values comparison mode is completed.

M1152

Set DHSZ instruction as frequency control mode

M1153

DHSZ frequency control mode has been executed.

M1235 ~ M1245

Designating the counting direction of high speed counters C235 ~ C245

When M12□□ = Off, C2□□ will perform a counting up.

When M12□□ = On, C2□□ will perform a counting down.

M1246 ~ M1255

Monitor the counting direction of high speed counters C246 ~ C255

When M12□□ = Off, C2□□ will perform a counting up.

When M12□□ = On, C2□□ will perform a counting down.

M1260

X5 as the reset input signal of all high speed counters

M1261

High-speed comparison flag for DHSCR instruction

M1264

Disable the external control signal input point of HHSC0 reset signal point (R)

M1265

Disable the external control signal input point of HHSC0 start signal point (S)

M1266

Disable the external control signal input point of HHSC1 reset signal point (R)

M1267

Disable the external control signal input point of HHSC1 start signal point (S)

M1268

Disable the external control signal input point of HHSC2 reset signal point (R)

M1269

Disable the external control signal input point of HHSC2 start signal point (S)

M1270

Disable the external control signal input point of HHSC3 reset signal point (R)

M1271

Disable the external control signal input point of HHSC3 start signal point (S)

M1272

Internal control signal input point of HHSC0 reset signal point (R)

M1273

Internal control signal input point of HHSC0 start signal point (S)

M1274

Internal control signal input point of HHSC1 reset signal point (R)

M1275

Internal control signal input point of HHSC1 start signal point (S)

M1276

Internal control signal input point of HHSC2 reset signal point (R)

M1277

Internal control signal input point of HHSC2 start signal point (S)

M1278

Internal control signal input point of HHSC3 reset signal point (R)

M1279

Internal control signal input point of HHSC3 start signal point (S)

M1289

High speed counter I010 interruption forbidden

M1290

High speed counter I020 interruption forbidden

M1291

High speed counter I030 interruption forbidden

M1292

High speed counter I040 interruption forbidden

M1293

High speed counter I050 interruption forbidden

M1294

High speed counter I060 interruption forbidden

M1312

C235 Start input point control

M1313

C236 Start input point control