7 Application Instructions API 50-99

D V P - P L C A P P L I C AT I O N M A N U A L

7-24

API Mnemonic

Operands

Function

56

SPD

Speed Detection

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T

C

D

E

F

S

1

*

S

2

*

*

*

*

*

*

*

*

*

*

*

D

*

*

*

SPD: 7 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

S

1

: External pulse input terminal S

2

: Pulse receiving time (ms) D: Detected result

Explanations:

1.

See the specifications of each model for their range of use.

2.

Flag: M1100 (SPD instruction performs sampling for one time)

3.

External pulse input terminals designated in S

1

for all series MPU:

MPU
Input

ES/EX/SS (V5.7and above)

SA/SX/SC

EH/EH2/SV

Available input points

X1, X2

X0, X1, X2

X0 ~ X3

4.

For SA/SX (V1.4 and above) series MPU and SC (V1.2 and above) series MPU, the new X0 and X1 can be

used together with A-B phase input points. When “A ahead of B” detection result is a positive value and “B

ahead of A” detection result is a negative value, the multiplied frequency of the counter can be set by D1022.

5.

The received number of pulses of the input terminal designated in S

1

is calculated within the time (in ms)

designated in S

2

. The result is stored in the register designated in D.

6.

D

will occupy 5 consecutive devices. D + 1 and D are the detected value obtained from the previous pulses; D

+3 and D + 2 are the current accumulated number of values; D + 4 is the counting time remaining (max.

32,767ms).

7.

Pulse frequency detection for all series:

MPU

ES/EX/SS (V5.7 and above)

SA/SX/SC

EH/EH2/SV

Max. frequency

X1 (20KHz), X2 (10KHz)

X0/X1 A-B phase input (4KHz)

X1 (30KHz), X2 (10KHz)

X0/X1 (100KHz)

X2/X3 (10KHz)

8.

This instruction is mainly used for obtaining a proportional value of rotation speed. The result D and rotation

speed will be in proportion. The following equation is for obtaining the rotation speed of motor.

N: Rotation

speed

n: The number of pulses produced per rotation

N=

( )

(

)

rpm

10

×

nt

0

D

60

3

t:

Detecting time designated in S

2

(ms)

9.

The X input point designated by this instruction cannot be used again as the pulse input terminal of the high

speed counter or as an external interruption signal.

10. When M1036 in SC (V1.4 and above) series MPU is enabled, SPD instruction can detect the speeds at X0 ~ X5