10 Application Instructions API 200-249

DVP-PLC Application Manual

10-7

API Mnemonic

Operands

Function

215~

217

D LD#

Contact Logical Operation LD#

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX KnY KnM KnS T

C

D

E

F

S

1

*

* *

*

*

*

*

*

*

*

*

S

2

*

*

*

*

*

*

*

*

*

*

*

LD#: 5 steps

DLD#: 9 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

S

1

: Data source device 1 S

2

: Data source device 2

Explanations:

1.

See the specifications of each model for the range of operands.

2.

This instruction compares the content in S

1

and S

2

. If the result is not “0”, the continuity of the instruction is

enabled. If the result is “0”, the continuity of the instruction is disabled.

3. LD#

(

#:

&, |, ^

)

instruction is used for direct connection with BUS.

API No.

16 -bit

instruction

32 -bit

instruction

Continuity

condition

No-continuity

condition

215 LD& DLD&

S

1

& S

2

0

S

1

& S

2

=0

216 LD|

D

LD|

S

1

| S

2

0

S

1

| S

2

=0

217 LD^ DLD^

S

1

^ S

2

0

S

1

^ S

2

=0

4.

&:

Logical “AND” operation

5.

|:

Logical “OR” operation

6.

^:

Logical “XOR” operation

7.

When 32-bit counters (C200 ~ C255) are used in this instruction for comparison, make sure to adopt 32-bit

instruction (DLD#). If 16-bit instructions (LD#) is adopted, a “program error” will occur and the ERROR

indicator on the MPU panel will flash.

Program Example:

1. When the result of logical AND operation of C0 and C10 ≠ 0, Y10 = On.

2. When the result of logical OR operation of D200 and D300 ≠ 0 and X1 = On, Y11 = On will be retained.

3. When the result of logical XOR operation of C201 and C200 ≠ 0 or M3 = On, M50 = On.

M3

DLD

C201

C200

M50

LD

C0

C10

LD

D200

D300

SET

X1

&

^

I

Y011

Y10