8 Application Instructions API 100-149

DVP-PLC Application Manual

8-11

API Mnemonic

Operands

Function

102

FWD

Forward Running of VFD-A

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX KnY KnM KnS T

C

D

E

F

S

1

*

*

*

S

2

*

*

*

n

*

*

*

FWD: 7 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

API Mnemonic

Operands

Function

103

REV

Reverse Running of VFD-A

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX KnY KnM KnS T

C

D

E

F

S

1

*

*

*

S

2

*

*

*

n

*

*

*

REV: 7 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

API Mnemonic

Operands

Function

104

STOP

Stop VFD-A

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX KnY KnM KnS T

C

D

E

F

S

1

*

*

*

S

2

*

*

*

n

*

*

*

STOP: 7 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

S

1

: Address of communication device S

2

: Rotation frequency of AC motor drive n: Target to be instructed

Explanations:

1. Range

of

S

1

: K0 ~ K31

2. Range

of

n

: K1 or K2

3. See the specifications of each model for their range of use.

4. ES series MPU does not support E, F index register modification.

5. Flags: See API 80 RS for explanations on M1120 ~ M1131, M1140 ~ M1143

6. FWD/REV/STOP are handy instructions exclusively for Delta VFD-A/H series AC motor drive to perform

forward running/reverse running/stop. Be sure to set up communication time-out (D1129) when executing this

instruction.

7. S

2

= operation frequency of AC motor drive. Set frequency in A-series AC motor drive: K0 ~ K4,000 (0.0Hz ~