9 Application Instructions API 150-199

DVP-PLC Application Manual

9-7

3.

When in RTU mode, the user stores the data to be written in the designated register D50 in hex format. The

data sent back from AC motor drive are stored in D1070 ~ D1077.

4.

When In ASCII mode or RTU mode, PLC will store the data to be sent in D1256 ~ D1295. If necessary, the

user can move the data to other general registers by using MOV, DMOV or BMOV instruction. Other

instructions of ES/EX/SS do not function on the data in D1256 ~ D1295.

5.

After receiving the data sent back from AC motor drive is completed, PLC will auto-check if the received data

are incorrect. M1140 will be On if there is an error.

6.

If the device address is illegal to a designated communication device, the communication device will respond

with an error message and PLC will store the error code in D1130 and M1141 = On. For example, if 8000H is

illegal to VFD-S, M1141 will be On and D1130 = 2. See user manual of VFD-S for error codes.

7.

After M1140 = On or M1141 = On, PLC will send another correct datum to AC motor drive. If the data sent back

from AC motor drive is correct, M1140 and M1141 will be reset.

H 87

MOV

M1002

D 1120

SET

M1120

K100

MOV

D 1129

M1127

R ST

M1127

M1143

X10

Set up communication
protocol 9600, 8, E, 1

Retain communication protocol

Communication
time-out 100ms

MOD R W

K16

K1

X0

H 2000

D 50

K8

Address of
communi-
cat ion
device K1

Function
code K16:
write many
word data

Data address
H2000

Register
for st oring
the data

Data length
(word)

SET

X0

M1122

Set up sending request

Process of received data

ASCII mode : The

received data are stored in special registers D1070 ~ D1078 in ASCII format.

Sending/receiving of data is comp leted. The flag is reset.

RTU mode : The

.

received data are stored in sp ecial registers D1070~1078 in hex format

8.

ASCII Mode: When PLC is connected to VFD-S AC motor drive.

PLC

Ö VFD-S, PLC sends: “01 10 2000 0002 04 0012 1770 30

VFD-S

Ö PLC, PLC receives: “01 10 2000 0002 CD

Registers for sent data (sending messages)

Register

DATA

Explanation

D1256 Low

‘0’

30 H

ADR 1

D1256 High

‘1’

31 H

ADR 0

Address of AC motor drive: ADR (1,0)

D1257 Low

‘1’

31 H

CMD 1

D1257 High

‘0’

30 H

CMD 0

Instruction code: CMD (1,0)

D1258 Low

‘2’

32 H

D1258 High

‘0’

30 H

D1259 Low

‘0’

30 H

D1259 High

‘0’

30 H

Data Address

D1260 Low

‘0’

30 H

D1260 High

‘0’

30 H

D1261 Low

‘0’

30 H

D1261 High

‘2’

32 H

Number of Registers