Delta Electronics Programmable Logic Controller DVP04DA-H2 User Manual

Warning, Introduction, Specifications

background image

Warning

Please read this instruction carefully before use.

Switch off the power before wiring.

DVP04DA-H2 is an OPEN-TYPE device and therefore should be installed in an enclosure free of airborne dust,
humidity, electric shock and vibration. The enclosure should prevent non-maintenance staff from operating the

device (e.g. key or specific tools are required to open the enclosure) in case danger and damage on the device may
occur.

DO NOT connect input AC power supply to any of the I/O terminals; otherwise serious damage may occur. Check

all the wiring again before switching on the power.

DO NOT touch any terminal when the power is switched on. DO NOT touch any internal circuit in 1 minute after
the power is switched off.

Make sure the groud terminal

is correctly grounded in order to prevent electromagnetic interference.

Introduction

Model Explanation & Peripherals

Thank you for choosing Delta DVP series PLC. The data in DVP04DA-H2 can be read or written

FROM/TO instructions given by the program of DVP-EH2 series MPU. The analog signal output module

receives 4 groups of 12-bit digital data from PLC MPU and converts the data into 4 points of analog

signals for output in either voltage or current.

You can select voltage or current output by wiring. Range of voltage output: 0V ~ +10V DC (resolution:

2.5mV). Range of current output: 0mA ~ 20mA (resolution: 5µA).

Product Profile (Indicators, Terminal Block, I/O Terminals)

Unit: mm

D

-

V

+

I

+

C

O
M

2

4

V

0

V

V

+

I

+

V

+

I

+

C

O

M

D

+

C

O

M

8

C

H

1

C

H

3

C

H

4

R

S

-4

8

5

F

G

V

+

F

G

C

O

M

F

G

I

+

C

H

2

1

DIN rail (35mm)

6

Terminals

2

Connection port for extension modules

7

Mounting hole

3

Model name

8

I/O terminals

4

POWER, ERROR, D/A indicator

9

Mounting port for extension modules

5

DIN rail clip


ENGLISH

External Wiring

V+

I+

COM

V+

I+

COM

24+
24-

DC/DC

+15V

-15V

AG

FG

FG

CH1

CH1

0V~+10V

*2

*3

0mA~20mA

DC24V

CH4

CH4

AC drive, recorder,
scale valve...

AC drive, recorder,
scale valve...

voltage output

shielding cable *1

shielding cable *1

current output

converter

terminal of
power module

system grounding

class 3 grounding
(100

or less)

Note:

1.

When performing analog output, please isolate other power wirings.

2.

If the ripples at the loaded input terminal are too significant that causes noise interference on the wiring, connect the

wiring to 0.1 ~ 0.47µF 25V capacitor.

3.

Please connect the terminal on both the power modules and DVP04DA-H2 to the system earth point and ground the

system contact or connect it to the cover of power distribution cabinet.

4.

DO NOT wire empty terminals .

Specifications

Digital/Analog (4D/A)

module

Voltage output

Current output

Power supply voltage

24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)

Analog output channel

4 channels/module

Range of analog output

0 ~ 10V

0 ~ 20mA

Range of digital data

0 ~ 4,000

0 ~ 4,000

Resolution

12 bits (1

LSB

= 2.5mV)

12 bits (1

LSB

= 5µA)

Output impedance

0.5Ω or lower

Overall accuracy

±0.5% when in full scale (25°C, 77°F)

±1% when in full scale within the range of 0 ~ 55°C, 32 ~ 131°F

Responding time

3ms × the number of channels

Max. output current

10mA (1KΩ ~ 2MΩ)

-

Tolerable load impedance

-

0 ~ 500Ω

Digital data format

11 significant bits out of 16 bits are available; in 2’s complement.

Isolation

Internal circuit and analog output terminals are isolated by optical coupler.

No isolation among analog channels.

Protection

Voltage output is protected by short circuit. Short circuit lasting for too long may cause

damage on internal circuits. Current output can be open circuit.

Communication mode

ASCII/RTU mode.

(RS-485)

Communication speed: 4,800/9,600/19,200/38,400/57,600/115,200 bps.

ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1).

RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1).

RS-485 cannot be used when connected to PLC MPU.

When connected to
DVP-PLC MPU in series

The modules are numbered from 0 to 7 automatically by their distance from MPU. No.0 is
the closest to MPU and No.7 is the furthest. Maximum 8 modules are allowed to connect to
MPU and will not occupy any digital I/O points.

Other Specifications

Power supply

Max. rated power
consumption

24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%), 4.5W, supplied by external power.

Environment

Operation/storage

Operation: 0°C ~ 55°C (temperature); 50 ~ 95% (humidity); pollution degree 2
Storage: -25°C ~ 70°C (temperature); 5 ~ 95% (humidity)

Vibration/shock
immunity

International standards: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 & IEC 68-2-27
(TEST Ea)

Control Registers

CR

#

RS-485

parameter

address

Latched

Register content

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

#0

H’4032

○ R Model name

Set up by the system. DVP04DA-H2 model code = H’6401.

The user can read the model name from the program and see
if the extension module exists.

Reserved

CH4

CH3

CH2

CH1

#1

H’4033

○ R/W Output mode setting

Output mode: Default = H’0000

Mode 0: Voltage output (0V ~ 10V)

Mode 1: Voltage output (2V ~ 10V)

Mode 2: Current output (4mA ~ 20mA)

Mode 3: Current output (0mA ~ 20mA)

CR#1: The working mode of the four channels in the analog input module. There are 4 modes for each channel which can

be set up separately. For example, if the user needs to set up CH1: mode 0 (b2 ~ b0 = 000); CH2: mode 1 (b5 ~ b3 = 001),

CH3: mode 2 (b8 ~ b6 = 010) and CH4: mode 3 (b11 ~ b9 = 011), CR#1 has to be set as H’000A and the higher bits (b12 ~

b15) have to be reserved. Default value = H’0000.

#6

H’4038

R/W CH1 output value

#7

H’4039

R/W CH2 output value

#8

H’403A

R/W CH3 output value

#9

H’403B

R/W CH4 output value

Range of output value at CH1 ~ CH4: K0 ~ K4,000

Default = K0 (unit: LSB)

#18 H’4044

○ R/W Adjusted OFFSET value of CH1

#19 H’4045

○ R/W Adjusted OFFSET value of CH2

#20 H’4046

○ R/W Adjusted OFFSET value of CH3

#21 H’4047

○ R/W Adjusted OFFSET value of CH4

Range of OFFSET at CH1 ~ CH4: K-2,000 ~ K2,000

Default = K0 (unit: LSB)

#24 H’404A

○ R/W Adjusted GAIN value of CH1

#25 H’404B

○ R/W Adjusted GAIN value of CH2

#26 H’404C

○ R/W Adjusted GAIN value of CH3

Range of GAIN at CH1 ~ CH4: K0 ~ K4,000

Default = K2,000 (unit: LSB)

CR

#

RS-485

parameter

address

Latched

Register content

b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0

#27 H’404D

○ R/W Adjusted GAIN value of CH4

CR#18 ~ CR#27: Please note that: GAIN value - OFFSET value = +400

LSB

~ +6,000

LSB

(voltage or current). When GAIN -

OFFSET is small (steep oblique), the resolution of output signal will be finer and variation on the digital value will be

greater. When GAIN - OFFSET is big (gradual oblique), the resolution of output signal will be rougher and variation on the

digital value will be smaller.

#30 H’4050

R Error status

Register for storing all error status.

See the table of error status for more information.

CR#30: Error status value (See the table below)

Error status

Content

b15 ~ b8

b7

b6

b5

b4

b3

b2

b1

b0

Abnormal power supply

K1 (H’1)

0

0

0

0

0

0

0

1

Incorrect analog input value

K2 (H’2)

0

0

0

0

0

0

1

0

Incorrect mode setting

K4 (H’4)

0

0

0

0

0

1

0

0

OFFSET/GAIN error

K8 (H’8)

0

0

0

0

1

0

0

0

Hardware malfunction

K16 (H’10)

0

0

0

1

0

0

0

0

Abnormal digital range

K32 (H’20)

0

0

1

0

0

0

0

0

Incorrect average times setting

K64 (H’40)

0

1

0

0

0

0

0

0

Instruction error

K128 (H’80)

Reserved

1

0

0

0

0

0

0

0

Note: Each error status is determined by the corresponding bit (b0 ~ b7) and there may be more than 2 errors occurring at the

same time. 0 = normal; 1 = error.

Example: Iif the digital input exceeds 4,000, error (K2) will occur. If the analog output exceeds 10V, both analog input value
error K2 and K32 will occur.

#31 H’4051

○ R/W Communication address setting

For setting up RS-485 communication address.

Range: 01 ~ 254. Default = K1

#32 H’4052

○ R/W

Communication speed (baud

rate) setting

Default = H’0002. For setting up communication speed: 4,800

/9,600/19,200/38,400/57,600/115,200 bps.

ASCII data format: 7-bit, even bit, 1 stop bit (7, E, 1).

RTU data format: 8-bit, even bit, 1 stop bit (8, E, 1).

b0: 4,800 bps. b1: 9,600 bps (Default).

b2: 19,200 bps. b3: 38,400 bps.

b4: 57,600 bps. b5: 115,200 bps.

b6 ~ b13: Reserved.

b14: High/low bit exchange of CRC checksum (only valid in

RTU mode).

b15: Switch between ASCII/RTU mode. 0 = ASCII mode

(Default).

Reserved

CH4

CH3

CH2

CH1

#33 H’4053

○ R/W

Return to default setting;

OFFSET/GAIN tuning

authorization

Default = H’0000. Take the setting of CH1 for example:

1. When b0 = 0, the user is allowed to tune CR#18

(OFFSET) and CR#24 (GAIN) of CH1. When b0 = 1, the
user is not allowed to tune CR#18 (OFFSET) and CR#24
(GAIN) of CH1.

2. b1 represents whether the OFFSET/GAIN tuning registers

are latched. b1 = 0 (default, latched); b1 = 1 (non-latched).

3. When b2 = 1, all settings will return to default values.

(except CR#31, CR#32)

CR#33: For authorizations on some internal functions, e.g. OFFSET/GAIN tuning. The latched function will store the

output setting in the internal memory before the power is cut off.

#34 H’4054

○ R Firmware version

Displaying the current firmware version In hex; e.g. version

1.0A is indicated as H’010A.

#35 ~ #48

For system use.

Symbols:

○:Latched (when written in through RS-485 communication);

: Non-latched;

R: Able to read data by FROM instruction or RS-485 communication;

W: Able to write data by TO instruction or RS-485 communication.

LSB (Least Significant Bit):

For voltage output: 1

LSB

= 10V/4,000 = 2.5mV. For current output: 1

LSB

= 20mA/4,000 = 5µA.

CR#0 ~ CR#34: The corresponding parameter addresses H’4032 ~ H’4054 are for users to read/write data by
RS-485 communication. When using RS-485, the user has to separate the module with MPU first.

a. Communication baud rate: 4,800/9,600/19,200/38,400/57,600/115,200 bps.

b. Modbus ASCII/RTU communication protocols: ASCII data format (7-bit, even bit, 1 stop bit (7, E, 1));

RTU data format (8-bit, even bit, 1 stop bit (8, E, 1)).

c. Function: H’03 (read register data); H’06 (write 1 word datum to register); H’10 (write many word data to

register).

d. Latched CR should be written by RS-485 communication to stay latched. CR will not be latched if written

by MPU through TO/DTO instruction.

Adjusting D/A Conversion Curve

Voltage output mode

CR#1 mode 0

GAIN = 5V (2,000

LSB

). OFFSET = 0V (0

LSB

).

CR#1 mode 1

GAIN = 6V (2,400

LSB

). OFFSET = 2V (800

LSB

).

GAIN

The voltage output value when the digital input value = K2,000.

Range: 0

LSB

~ +4,000

LSB

.

OFFSET

The voltage output value when the digital input value = K0.

Range: -2,000

LSB

~ +2,000

LSB

.

+2,000

+4,000

2V

5V

6V

10V

OFFSET

GAIN

V

o

lt

a

g

e

o

u

tp

u

t

Digital input

Mode 1

Mode 0

GAIN - OFFSET Range: +400

LSB

~ +6,000

LSB

.

Current output mode

CR#1 mode 2

GAIN = 12mA (2,400

LSB

). OFFSET = 4mA (800

LSB

).

CR#1 mode 3

GAIN = 10mA (2,000

LSB

). OFFSET = 0mA (0

LSB

).

GAIN

The current output value when the digital input value = K2,000.

Range: 0

LSB

~ +4,000

LSB

.

OFFSET

The current output value when the digital input value = K0.

Range: -2,000

LSB

~ +2,000

LSB

.

0

+2,000

+4,000

20mA

OFFSET

GAIN

12mA
10mA

4mA

C

u

rr

e

n

t

o

u

tp

u

t

Digital input

Mode 2

Mode 3

GAIN - OFFSET Range: +400

LSB

~ +6,000

LSB

.

注意事項

請在使用之前,詳細閱讀本使用說明書。

實施配線,務必關閉電源。

本機為開放型 (OPEN TYPE) 機殼,因此使用者使用本機時,必須將之安裝於具防塵、防潮及免於電擊/衝擊
意外之外殼配線箱內。另必須具備保護措施(如:特殊之工具或鑰匙才可打開)防止非維護人員操作或意外
衝擊本體,造成危險及損壞。

輸入電源不可連接於輸入

出信號端,否則可能造成嚴重的損壞,因此請在上電之前再次確認電源配線。

請勿在上電時觸摸任何端子。輸入電源切斷後,一分鐘之內,請勿觸摸內部電路。

本體上之接地端子 務必正確的接地,可提高產品抗雜訊能力。

產品簡介

說明及週邊裝置

感謝您採用台達 DVP 系列產品。DVP04DA-H2 類比信號輸出模組可透過 DVP-EH2 系列主機程式以指令
FROM/TO

來讀寫 DVP04DA-H2 類比信號輸出模組之資料。而類比信號輸出模組接受來自 PLC 主機的 4 組

12

位元數位資料,再將數位資料轉換為 4 點類比信號輸出(電壓或電流皆可)。

使用者可經由配線選擇電壓輸出或電流輸出。電壓輸出範圍 0V ~ +10V DC(解析度為 2.5mV)。電流輸出
範圍 0mA ~ 20mA(解析度為 5µA)。

產品外觀及各部介紹

尺寸單位:mm

D

-

V

+

I +

C

O

M

2

4

V

0

V

V

+

I +

V

+

I +

C

O

M

D

+

C

O

M

8

C

H

1

C

H

3

C

H

4

R

S

-4

8

5

F

G

V

+

F

G

C

O

M

F

G

I +

C

H

2

1 DIN 軌糟 (35mm)

6 端子

2 擴充機/擴充模組連接口

7 固定孔

3 機種名稱

8 端子配置

4 電源、錯誤及轉換指示燈

9 擴充機/擴充模組連接座

5 DIN 軌固定扣

繁體中文

外部配線

V+

I+

COM

V+

I+

COM

24+

24-

DC/DC

轉換器

+15V

-15V

AG

FG

FG

CH1

CH1

隔離線*1

電壓輸出

0V~+10V

*2

變頻器、記錄器

比例閥...

*3

隔離線*1

電流輸出

0mA~20mA

變頻器、記錄器
比例閥...

接至電源模
組之 端

接地

(接地阻抗 以下)

DC24V

系統接地點

CH4

100

CH4

註 1:類比輸出請與其他電源線隔離。

註 2:如果負載之輸入端漣波太大造成配線受雜訊干擾時,請連接 0.1 ~ 0.47µF 25V 之電容。
註 3:請將電源模組之 端及 DVP04DA-H2 類比信號輸出模組之 端連接到系統接地點,再將系統接點作接地或接到

配電箱之機殼上。

注意:空端子 請勿配線。

規格

數位/類比 (4D/A) 模組

電壓輸出

電流輸出

電源電壓

24V DC (20.4V DC ~ 28.8V DC) (-15% ~ +20%)

類比訊號輸出通道

4

通道/台

類比輸出範圍

0 ~ 10V

0 ~ 20mA

數位資料範圍

0 ~ 4,000

0 ~ 4,000

解析度

12 bits (1

LSB

= 2.5mV)

12 bits (1

LSB

= 5µA)

輸出阻抗

0.5Ω

或更低

總和精密度

±0.5%

在(25°C, 77°F)範圍內滿刻度時。±1% 在(0 ~ 55°C, 32 ~ 131°F)範圍內滿刻度時。

響應時間

3ms ×

通道數

最大輸出電流

10mA (1KΩ ~ 2MΩ)

容許負載阻抗

0 ~ 500Ω

數位資料格式

16

位元二補數,有效位 11 bits

隔離方式

內部電路與類比輸出端以光耦合器隔離,類比通道間未隔離。

保護

電壓輸出有短路保護但須注意長時間短路仍有可能造成內部線路損壞,電流輸出可開路。

通訊模式 (RS-485)

包含 ASCII/RTU 模式,通訊速率可選(4,800/9,600/19,200/38,400/57,600/115,200 bps),ASCII 模
式資料格式固定為 7 bits、偶位元、1 stop bit (7, E, 1),RTU 模式資料格式固定為 8 bits、偶位元、
1 stop bit (8, E, 1)

。當與 PLC 主機串接時,RS-485 通訊無法使用。