Delta Electronics Programmable Logic Controller DVP-PLC User Manual

Page 502

background image

9 Application Instructions API 150-199

DVP-PLC Application Manual

9-30

API Mnemonic

Operands

Function

159

D DRVA

Drive to Absolute

Controllers

ES/EX/SS SA/SX/SC EH/SV

Bit Devices

Word Devices

Program Steps

Type

OP

X Y M S K H

KnX

KnY KnM KnS T

C

D

E

F

S

1

*

*

*

*

*

*

*

*

*

*

*

S

2

*

*

*

*

*

*

*

*

*

*

*

D

1

*

D

2

*

*

*

DRVA: 9 steps

DDRVA: 17 steps

PULSE 16-bit 32-bit

ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV ES EX SS SA SX SC EH SV

Operands:

S

1

: Number of output pulses (absolute designation) S

2

: Pulse output frequency D

1

: Pulse output device

(please use transistor output module) D

2

: Output device for the signal of rotation direction

Explanations:

1.

See remarks for the setting range of S

1

, S

2

, D

1

and D

2

.

2.

S

1

and S

2

of SC series MPU only support device K, H and D.

3.

Flag: see remarks of API 158 DRVI for more details.

4.

S

1

is the number of output pulses (absolute designation). For EH/EH2/SV series MPU, the 16-bit instruction

can designate the range -32,768 ~ +32,767. The range designated by 32-bit instruction is -2,147,483,648 ~

+2,147,483,647. For SC series MPU, the 32-bit instruction can designate the range -2,147,483,648 ~

+2,147,483,647. “+/-” signs indicate forward/backward directions.

5.

S

2

is the designated pulse output frequency. For EH/EH2/SV series MPU, the 16-bit instruction can designate

its range 10 ~ 32,767Hz. The range designated by 32-bit instruction is 10 ~ 200,000Hz. For SC series MPU,

the 32-bit instruction can designate the range 100 ~ 100,000Hz.

6.

EH series MPU has two groups of A/B phase pulse output, CH0 (Y0, Y1) and CH1 (Y2, Y3). EH2/SV series

MPU has four groups of A/B phase pulse output, CH0 (Y0, Y1), CH1 (Y2, Y3), CH2 (Y4, Y5) and CH3 (Y6, Y7).

See remarks for the setup methods.

7.

Pulse output device D

1

in different models

Model

SC MPU

EH MPU

EH2/SV MPU

Pulse output end

Y10, Y11

Y0, Y2

Y0, Y2, Y4, Y6

8. When

S

1

is larger than the current relative position, D

2

will be Off; when S

1

is smaller than the current relative

position, D

2

will be On. D

2

will not be Off immediately after the pulse output is over; it will be Off only when the

drive contact of the instruction turns Off.

9.

For EH/EH2/SV series MPU, S

1

is

- The 32-bit data stored in the present value registers D1337 (high word) and D1336 (low word) of CH0 (Y0,

Y1).

- The 32-bit data stored in the present value registers D1339 (high word) and D1338 (low word) of CH1 (Y2,

Y3).

- The 32-bit data stored in the present value registers D1376 (high word) and D1375 (low word) of CH2 (Y4,

Y5).

- The 32-bit data stored in the present value registers D1378 (high word) and D1377 (low word) of CH3 (Y5,