2 signal levels, 3 signal designations – HEIDENHAIN TNC 407 (243 020) Technical Manual User Manual
Page 663
2.3.2 Signal levels
On a RS-422/V.11 interface, the signals are both transmitted and received as differential voltage.
A positive differential voltage corresponds to logic "0" (OFF), and a negative differential voltage to
logic "1" (ON).
Differential voltages between
Vdmin = 2V and Vdmax = 5V
are transmitted and the control unit detects the differential voltages between
Vdmin = 0.2V and Vdmax = 6V
as a logically defined level.
– 0.2
Ud [V]
Ausgang
Output
Eingang
Input
"0"
OFF
"1"
ON
+ 0.2
–
0.
2
–
0.
5
–
0.
6
+
0.
2
+
0.
5
+
0.
6
"1"
ON
"0"
OFF
2.3.3 Signal designations
With a RS-422/V.11 interface, the following signals are transmitted as differential signals:
Data signals:
TxD, TxD
RxD, RxD
Control and verification signals:
RTS, RTS
CTS, CTS
DSR, DSR
DTR, DTR
This manual is related to the following products: