16 Commissioning and start-up procedure

01.98

16.3.5 Fixing the software limit switch ranges

Determine the software limit switch ranges (see section "Machine axes") as follows:

In "Manual operation" mode select the REF-

display with the MOD key.

Position-displays show the distance to the

machine datum .

Move all axes with the aid of the direction keys or

the handwheel in positive and negative direction to

just before the EMERGENCY STOP limit switches. Note the

values in the positional-displays and their sign.

Enter the noted values in MP910 or MP920.

Select actual-value display with MOD key.

16.3.6 Optimizing the control with lag (MP1390 = 1)

The following provisional values can be entered for the machine parameters which determine the
control characteristics:

Machine parameter

Function

provisional entry value

MP1050

Analogue voltage for rapid
traverse

9 V

MP1060

Acceleration

As measured on the machine
(see "Preparation of the machine")

MP1810

kv factor

1

MP1820

Multiplication factor

1

MP1830

Kink point

Entry value =

max. mach. speed

Rapid traverse

·

%

100

These values can usually be further optimized.