TNC 407/TNC 415/TNC 425

4 Main Spindle

4-99

4.1.3 S-Override

The spindle speed can be altered within certain limits by the S-override potentiometer . These limits
are fixed by machine parameter MP3310. However, the upper spindle speed-limit from MP3515
cannot be exceeded by S-override.

The %-factor which is adjusted by S-override is kept in Word W492 and W764. However, W764 be
changed by the PLC. As soon as a different value is entered here it will be adopted by the NC. In this
way the %-factor can be influenced by the PLC .

If W764 is not changed by the PLC, the normal override-function remains active.

MP7620 bit 3 determines whether the override is effective in 1% steps or according to a non-linear
characteristic curve. In the non-linear characteristic, the lower range changes in 0.01% steps, and in
the range over 2.5% the step is 0.75%. The range of override values in W492 and W764 lies
between 1 and 150 in 1% steps for the linear characteristic, and between 0 and 15 000 for the non-
linear characteristic.

MP3310.0 Limit with S-override (maximum)

Entry: 0 to 150 [%]

MP3310.1 Limit with S-override (minimum)

Entry: 0 to 150 [%]

Word

Function

Set

Reset

W492

%-factor - spindle-override

NC

NC

(NC

PLC)

W764

%-factor - spindle override

NC; PLC

NC; PLC

(PLC

NC)

MP7620 Feed-rate and spindle override
Entry: %xx0x

Bit 3

Override in 1% steps or non-linear

0 = 1% steps
1 = non-linear