01.98

TNC 407/TNC 415/TNC 425

5 EMERGENCY STOP-routine

4-123

11. Maximum time during which the acknowledgement of

control readiness on X42/4 must go to 0. (t < 114 ms).

If exceeded

EMERGENCY STOP DEFECTIVE

12. Recognize the acknowledgement and set X41/34

(t < 20 ms).

13. Wait for control voltage.

RELAY EXT. DC VOLTAGE
MISSING

14. Normal control operation. Output and

control-is-ready acknowledgement signals are high.

15. Control voltage is switched off externally.

EMERGENCY STOP

16. After switching on the control voltage again, the

error message can be cancelled, followed by
normal control operation.

17. The control switches off the control-is-ready output

Flashing error-

(X41/34) after recognizing a fault.

message