3 status and coordinates 7-141, 1 read status information (module 9035) 7-141 – HEIDENHAIN TNC 407 (243 020) Technical Manual User Manual
Page 602

Possible errors:
- The module was not called from a SUBMIT Job.
- The specified string does not conform to the above conventions.
- There is no file with the specified name.
- The file to be selected is faulty.
- The module was called after the NC program started without a strobe marker being active.
- An incorrect string number was specified (out of range 0..3)
Call:
PS
B/W/D/K
CM
9033
Warning: Program execution ends here if a new
file is selected
PL
B/W/D
0: No error, file was already selected
1: String contains no valid file name
2: File not found
3: File is faulty
4: Wrong string number specified (0..3)
5: Call was not from a SUBMIT Job
6: Call once PGM started without strobe
Error status after call: M3171 =
0: File was already selected
1: Error condition see above
4.3 Status and Coordinates
4.3.1 Read Status Information (Module 9035)
Status information can be read with module 9035. A number is specified that identifies the desired
information.
The following status information is available:
Specified number:
Values read:
0
Main mode Editor
0 - Edit
1 - Test run
1
Main mode
Machine
0 - Approach reference points
1 - Manual mode
2 - Electronic handwheel
3 - Positioning with manual input
4 - Program run/single block
5 - Program run/full sequence