11 analogue inputs and outputs, 1 analogue inputs – HEIDENHAIN TNC 407 (243 020) Technical Manual User Manual
Page 331

4-206
TNC 407/TNC 415/TNC 425
11 Analogue inputs and outputs
01.98
11 Analogue inputs and outputs
11.1 Analogue inputs
Eight analogue inputs are available on the input/output extensions PL 410, PL 410 B (Id.-Nr 263 371
02) and PA 110. Of these, four are analogue inputs for Pt 100 thermistors (range 0
°
to 100
°
C;
resolution 0.5
°
) and four are analogue inputs for ± 10 V
DC (resolution 100 mV). The analogue values
are converted to digital values in the PL or PA and transferred to PLC words.
The content of the words can be further processed in the PLC for a variety of purposes (e.g.
compensating for thermal expansion, see section "Thermal compensation").
The word addresses in the PLC depend on whether the analogue inputs are on the first or second
extension. Machine parameter 4410 defines the extension on which the analogue inputs are found.
MP4410
Activate analogue input
Entry: %xx
Bit 0 =
0
No analogue inputs on extension #1
1
Analogue inputs on extension #1
Bit 1 =
0
No analogue inputs on extension #2
1
Analogue inputs on extension #2
Assignment of word addresses to the analogue inputs:
Input
PA
Input
PL
First
extension
Second
extension
Function
Set
Reset
X2
X3
X4
X5
X15
X16
X17
X18
W496
W498
W500
W502
W464
W466
W468
W470
Voltage input 0
Voltage input 1
Voltage input 2
Voltage input 3
NC
NC
X7
X8
X9
X10
X19
X20
X21
X22
W504
W506
W508
W510
W472
W474
W476
W478
Temperature input 0
Temperature input 1
Temperature input 2
Temperature input 3
NC
NC
Internal value range:
Voltage input:
−
100 to +100 (
−
10V to +10V)
Temperature input:
0 to 200 (0°C to 100°C)