2 Input/output of machine parameters
01.98
2.2 Activating the machine parameter settings
After the values for the machine have been entered, exit the machine parameter list by pressing the
END
- key. Missing or incorrect entries result in error messages from the control that prompt you
to correct your entry.
The following errors are displayed:
Entry error
Meaning
0
No MP number found
1
Invalid MP number
2
No separator ";" found
3
Entry value incorrect
4
MP doubly defined
5
MP not defined
6
MP can not be stored
If the control does not recognise any errors, it automatically exits the machine parameter editor and
is ready for operation.
If during commissioning no entries are made in the parameter list (MP NAME), the TNC will
generate a standard machine parameter list when the END
key is pressed. In this list the TNC is
defined as a programming station with the HEIDENHAIN standard colours. All other machine
parameters assume the minimum value.
It is also possible to keep several machine parameter lists and load the desired list into the TNC
when needed. The desired list can be selected in the machine parameter editor by pressing the
PGM NAME key and the SELECT soft key. The parameter list which is active when you exit the
machine parameter editor goes into effect.
2.3 Changing the entry values
After a machine parameter list has been created, it can be changed either through the machine
parameter editor or directly through the PLC.
2.3.1 Manual input
Call the machine parameter editor through the MOD function "code number".
Enter the code number 95 148 to access the complete list of machine parameters.
Entering the code number 123 opens a partial list of machine parameters. These are the machine
parameters that may be changed by the control user (see User's Manual for TNC 407/TNC 415).
The machine parameters which can be changed with the code number 123 are marked in the
following list with CN 123.
Exit the machine parameter editor by pressing the END
key.