16 Commissioning and start-up procedure
16.3.7 Optimizing the control with feedforward control (MP1390 = 0)
The following provisional values can be entered for the machine parameters which determine the
control characteristics:
Machine parameter
Function
Provisional entry value
MP1050
Analogue voltage for rapid
traverse
9 V
MP1060
Acceleration
As measured on the machine
(see "Preparation of the machine")
MP1510
kv factor
1
MP1520
Position approach
0.5 [m/min]
These values can usually be further optimized.
Optimize kv factor
Connect storage oscilloscope to tachometer
of the servo-amplifier of the X axis.
Enter following program in
"PROGRAMMING AND EDITING"
operating mode:
LBL 1
X 100
1)
R0 F MAX
X 0 R0 F MAX
CALL LBL 1 REP 100/100
Press machine START button in the
"PROGRAM RUN/SINGLE BLOCK"
operating mode.
Machine runs.
kv factor MP1510: Increase entry value until position loop oscillates.
U [V]
t [ms]
kv factor MP1510: Reduce entry value until no oscillations can be detected.
U [V]
t [ms]
1)
Program the traverse paths for the axis concerned as large as possible.