Basic System Operation

3.3.1 Overview of Scan Processing

3-10

3.3 Scan Processing

3.3.1 Overview of Scan Processing

There are three types of MP940 scan processing: S (system) scans, H (high-speed) scans,
and L (low-speed) scans. Scan processing is executed using time slicing within the S-scan
cycle, with the S scan as the basic cycle.

Background processing time for PP processing must be ensured by setting a ratio for alloca-
tion to background processing within the S scan cycle.

„

Types of Scans

„

Service Scans for Each Function

Except for SVA, the scan for executing I/O processing can be selected for each function.

Scan Type

Details

S scan (system scan)

• Basic cycle for scan processing: Select 0.5, 1.0, 2.0, or

4.0 ms.

• S, H, and L scan processing is all executed with time slic-

ing within the S-scan cycle.

H scan (high-speed scan)

• Set as an integer multiple of S-scan cycle.
• Executed with time slicing within S-scan cycle.

L scan (low-speed scan)

• Set as an integer multiple of S-scan cycle.
• Executed with time slicing within S-scan cycle.

Function

Scans Possible for

Servicing

Remarks

CNTR

S/H/L

Processed in sync with S, H, or L.

LIO (DI/DO/AI/AO)

S/H/L

Processed in sync with S, H, or L.

MECHATROLINK
(distributed I/O, etc.)

H/L

Processed in sync with H, or L.

SVA

S/H

Scan fixed (not selectable).
Parameters can be set to select synchronization with the
Phase Control Mode and the Position Control Mode.
Phase Control Mode Synchronization Selection
(OBC0016)
0: H scan (default); 1: S scan
Position Control Mode Parameter Synchronization
Selection (OBC0017)
0: H scan; 1: S scan (default)