A.40, Display and outputs, Status and remedy for alarm – Yaskawa MP940 User Manual

Page 377: A.41

background image

SERVOPACK Inspection, Maintenance, and Troubleshooting

10.2.1 Troubleshooting Problems with Alarm Displays

10-10

„

A.40

A.40: Main Circuit DC Voltage Error Detected: Overvoltage

Display and Outputs

Note: OFF: Output transistor is OFF (alarm state).

ON: Output transistor is ON.

Status and Remedy for Alarm

„

A.41

A.41: Main Circuit Voltage Error Detected: Undervoltage

Display and Outputs

Note: OFF: Output transistor is OFF (alarm state).

ON: Output transistor is ON.

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

OFF

OFF

ON

OFF

Cause

Remedy

A

The power supply voltage is not within
the range of specifications.

Check power supply.

B

Load exceeds capacity of the Regener-
ative Unit.

Check specifications of load moment
of inertia and overhanging load.

C

Regenerative transistor is abnormal.

Replace SERVOPACK.

D

Rectifying diode defective.

E

SERVOPACK defective.

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

OFF

OFF

ON

OFF

E

A, B, C, D

A, D

During servomotor

operation

Occurred when main cir-

cuit power turned ON.

Occurred when the con-

trol power turned ON.