4.2.8 General-purpose Serial Definitions

4-18

When the Serial Definition Window is opened for the first time without any settings having previously
been made, a new message box will be displayed. Click the OK Button and then proceed to the next
operation.

4.2.8 General-purpose Serial Definitions

There are definition tabs for two circuits in the General-purpose Serial Settings Window.
Use both these tabs when making definitions.

„

Serial Communications Definitions

The following table shows the contents of the serial communications definitions.

„

Transmission Protocol

• MEMOBUS: Yaskawa standard MEMOBUS protocol
• MELSEC: Special protocol (control protocol format 1) for Mitsubishi Electric general

sequencer controller

• No protocol: Any data received at any time according to user application program.

INFO

Item

Contents

Circuit No.

Select by CIR# in Tab Window.

Transmission Protocol

Select MEMOBUS, MELSEC, or no protocol.

Master/Slave

Select Master or Slave operation.

Device Address

Set 0 for the Master, or 1 to 63 for Slaves.

Serial Interface

Select RS-232C, RS-485, or RS-422.

Transmission Mode

Select RTU, ASCII, or none.

Data Length

8 bits or 7 bits

Parity Bit

Even, odd, or none

Stop Bits

1 or 2

Baud Rate

Select the baud rate (unit: bps).

Transmission Delay

Set the delay time for the send/receive function (MSG-SND/RCV)
until a message is sent.

Automatic Reception

Specify whether there will be an automatic response to requests
from the master.

Reading Input Relays

Set the leading number and range for input relays read for automatic
responses.

Reading Input
Registers

Set the leading number and range for input registers read for auto-
matic responses.

Reading/Writing Coils

Set the leading number and range for coils read and written for
automatic responses.

Reading/Writing
Holding Registers

Set the leading number and range for holding registers read and
written for automatic responses.

Coil/Holding Register
Write Range

Set the write range for coils and holding registers read and written
for automatic responses.