11.3 Position Control

11-49

11

Operating Conditions

In the pattern shown in the above illustration on the previous page, the axis is stopped at an
absolute position of 10000 (pulses).

• Position reference: XREF = 10000 (pulses)

Ladder Logic Program Example

Fig 11.18 RUN Commands (DWG H03)

The example in the above illustration has been greatly simplified. In actual operation, each
register can be controlled from the user program.

DEND

RUN

OBC0810

RUNPB

IB00304

0000010000

XREF

OLC092

H0004

RUNMOD

OWC080

Set the position control mode to ON.

Position reference pulse (XREF)

(Absolute position: 10000)

Driver RUN command (RUN)

When IB00304 turns ON, position

control starts, and the axis is moved

to absolute position 10000. When

absolute position 10000 is reached,

the IBC080D positioning completed

signal turns ON.