2 start sequence – Yaskawa MP940 User Manual
Page 54

3.2 Start and Stop Sequences
3-7
3
3.2.2 Start Sequence
The MP940 makes a number of determinations at startup. If an error is detected, the ERR
indicator will flash and the error content will be indicated by the number of times the indica-
tor flashes. When the indicator is flashing, the CP-717 cannot be operated. For details on the
error content and the action to be taken, see Chapter 10 SERVOPACK Inspection, Mainte-
nance, and Troubleshooting. The following table shows the MP940 indicators.
Table 3.2 Indicators and Indicator Patterns
Type
Indicator
Meaning
RDY
RUN
ALM
BAT
Normal Lit
Unlit Unlit Unlit
The user program is stopped.
Lit
Lit
Unlit Unlit
The user program is executing normally.
Error
Unlit Unlit Lit
Unlit
Hardware reset status (while display is continu-
ing)
Unlit Unlit Unlit Unlit
During initial execution (while display is con-
tinuing)
Unlit
-
Lit
Unlit
A serious error has occurred.
Unlit Unlit
Flashing
Unlit
• Flashing twice: RAM error
• Flashing three times: ROM error
• Flashing four times: Peripheral LSI error
Alarm
-
-
-
Lit
Battery alarm
Lit
Lit
Lit
Unlit
• Calculation error
• I/O error
Reported to the system (S)
register (no indicator dis-
play)
Hardware status (power loss, RUN/STOP, test
mode, etc.)
Other
Flashing
Flashing
Unlit Unlit
Memory initialization has been completed for
the DIP switch settings.
RDY and RUN flash repeat-
edly at the same time.
Unlit Unlit Lit
Unlit
Offline test mode