6 serial communications protocol – Yaskawa MP940 User Manual
Page 104
4.2 Serial Communications Function
4-11
4
4.2.6 Serial Communications Protocol
The MP940 Module can handle various communications protocols, including the standard
Yaskawa MEMOBUS communications protocol.
It also provides the MELSEC communications protocol as a standard function for connect-
ing to Mitsubishi Electric controllers.
MEMOBUS Communications
MEMOBUS communications are message transmissions following the MEMOBUS proto-
col.
Table 4.2 Correspondence Between MEMOBUS Reference and Register Numbers
∗ 1.
MEMOBUS reference numbers are leading numbers used by Yaskawa
MEMOBUS protocol messages. They are allocated in the ranges
shown in the table to coils, input relays, input registers, and holding
registers. The first digit represents the classification, and the follow-
ing digits are the start number beginning from 1.
∗ 2.
MEMOBUS commands are command codes set in the MEMOBUS
protocol.
∗ 3.
Leading numbers are initial addressed used by the MP940, and they all
begin from 0 (zero).
∗ 4.
Register numbers are numbers for each register that correspond to the
leading numbers. These register numbers can be designated for offset
by the system functions MSG-SND and MSG-RCV, along with coils,
input relays, input registers, and holding registers.
For example, with Yaskawa GL:
Classification
MEMOBUS
Reference Numbers
*1
MEMOBUS
Commands
*2
MP940
Leading
Number
*3
Register
Number
*4
Coils
000001 - 0XXXXX
01H, 05H, 0FH
000000-
MB000000-
Input relays
100001 - 1XXXXX
02H
00000-
IB00000-
Input registers
300001 - 3XXXXX
04H
00000-
IW0000-
Holding
registers
400001 - 4XXXXX
05H
00000-
MW00000-