10.2 Troubleshooting

10-21

10

„

A.b1

A.b1: Reference Speed Input Read Error

Display and Outputs

Note: OFF: Output transistor is OFF (alarm state).

Status and Remedy for Alarm

„

A.b2

A.b2: Reference Torque Input Read Error

Display and Outputs

Note: OFF: Output transistor is OFF (alarm state).

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

OFF

OFF

OFF

OFF

Cause

Remedy

A

Error in reference read-in unit (A/D
Converter, etc.).

Reset alarm and restart operation.

B

Reference read-in unit faulty (A/D
Converter, etc.).

Replace SERVOPACK.

C

Circuit board (1PWB) defective.

Replace SERVOPACK.

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

OFF

OFF

OFF

OFF

C

A,B

During servomotor

operation

At power ON