SERVOPACK Inspection, Maintenance, and Troubleshooting

10.2.1 Troubleshooting Problems with Alarm Displays

10-12

„

A.71

A.71: Overload: High Load

The alarm output, status, and remedy for A.71 are the same as for A.72.

„

A.72

A.72: Overload: Low Load

Display and Outputs

Note: OFF: Output transistor is OFF (alarm state).

ON: Output transistor is ON.

Status and Remedy for Alarm

Alarm Outputs

Alarm Code Outputs

ALM Output

ALO1

ALO2

ALO3

ON

ON

ON

OFF

Cause

Remedy

A

Servomotor wiring incorrect or dis-
connected.

Check wiring and connectors at servomotor.

B

Load greatly exceeds rated torque.

Reduce load torque and inertia. Otherwise,
replace with larger capacity servomotor.

C

Circuit board (1PWB) defective.

Replace SERVOPACK.

C

A

B

B

When servo ON (/S-

ON) signal turned ON

When speed reference

input

No servomotor

rotation

During normal

operation

At power ON