System service execution status, System i/o error status – Yaskawa MP940 User Manual
Page 360
9.2 System Errors
9-15
9
Table 9.6 User Operation Error Status - 4
System Service Execution Status
Table 9.7 Latest Data Trace Record Number
System I/O Error Status
Error Code
Error Contents
User
System Default
Integer - Real
Number Oper-
ations
1000H
Index error within DWG
No
Re-executed with i, j = 0
2000H
Index error within function
No
Re-executed with i, j = 0
Integer Opera-
tion
x060H to
x077H
(x = 1, 2)
Index error within integer system func-
tion
No
The A register remains the same.
x06DH: PI
x06DH: PD
x06FH: PID
x070H: LAG
x071H: LLAG
x072H: FGN
x073H: IFGN
x074H: LAU
x075H: SLAU
x076H: FGN
x077H: IFGN
Name
Register No.
Remarks
System Error Count
SW00090
System Error Code
SW00091
Failure Occurrence Count
SW00092
Failure Restoration Count
SW00093
Reserved by System
SW00094 to
SW00097
(Not used.)
Existence Of Data Trace Definition
SW00098
Bit 0 to 3 = Group 1
Definition exists = 1, No definition = 0
Data Trace Execution Status
SW00099
Bit 0 to 3 = Group 1
Trace executing = 1, Trace stopped = 0
Name
Register No.
Remarks
Data Trace Group 1
SW00100
Latest record number
Name
Register No.
Remarks
I/O Error Count
SW00200
Number of I/O errors
Input Error Count
SW00201
Number of input errors
Input Error Address
SW00202
Latest input error address
(Register number of OWxxxx)
(For future use)
Output Error Count
SW00203
Number of output errors
Output Error Address
SW00204
Latest input error address
(Register number of OWxxxx)
(For future use)
Reserved by System
SW00205
(Not used.)
SW00206
SW00207