Page 261

background image

6.3 SVA Parameter Details

6-21

6

2

RUN Command
settings
(SVRUNCMD),
continued

Bit

12

Position Refer-
ence Value
Selection
(USE_BUF)

Set the reference method that is used for position
reference data. It is valid only when an OWC020:
Motion Command Code is used in Position Control
Mode.
0: Use OLC012 as directly as position reference
data.
1: Use OLC012 indirectly as the position buffer
number.

• The position buffer is located in the MP940

Module and must be written in the initial draw-
ing at startup.

• Refer to OBC021E, OBC021F, and OLC03A for

details on writing to the position buffer.

0

13

Speed Refer-
ence Value
Selection (SPD-
TYPE)

Set speed reference method for feed speed,
approach speed, and creep speed. It is valid only
when an OWC020: Motion Command Code is used
in Position Control Mode.
0: Set speed in reference units and sets rapid

traverse speed at OLC022. The setting unit for
OWC00A: Approach Speed and OWC00B:
Creep Speed are also 1 = 10

n

reference units/

min.

1: Set speed using a percentage and sets rapid

traverse speed at OLC015. The setting unit for
OWC00A: Approach Speed and OWC00B:
Creep Speed are also 1 = 0.01%.

Refer to 11.3.1 Prerequisites for Position Control.

0

No.

Name

Register

Number

Bit Name

Description

Default

OLxx12

 

1

2



100



256

100

Indirectly

specified

Directly

specified

Position reference

Position buffer pointer

Position buffer

Position reference data

Position reference data