6.4.6 Torque-related Parameters

6-62

6.4.6 Torque-related Parameters

Table 6.8 Torque-related Parameter Table

Parameter No.

Digit

Name (Setting

Range)

Details

Default

Control

Modes

Pn400
Torque Reference
Input Gain

0.1 V/rated
torque
10 to 100

Do not use this parameter when using an MP940.

30

Speed
Torque
Position

Pn401
Torque Reference
Filter Time Constant

0.01ms
0 to 65535

If there is machine vibration which may be caused by the servo-
drive, try adjusting the filter time constant in Pn401. This may
stop the vibration.
The above constant is the filter time constant of the torque refer-
ence to be set in the SERVOPACK. The smaller the value, the
faster the speed control response will be. There is, however, a
certain limit depending on machine conditions.

100

Speed
Torque
Position

Pn402
Forward Torque Limit

%
0 to 800

Use this parameter to limit the maximum output torque to protect
the machine and workpiece (internal torque limit).
This parameter sets the maximum torque limits for forward and
reverse rotation.
The torque limit function always monitors torque and outputs the
signals below when the limit is reached.
The following signals are output by the torque limit function.

• /CLT

Conditions for /CLT signal output: Allocate Pn50F.0 to any of
output terminals S01 to S03.

• Monitor Mode Un006

The torque limits are specified as a percentage of the rated
torque.

Note: If torque limit is set higher than the maximum torque of

the servomotor, the maximum torque of the servomotor is
the limit.

Application Example: Equipment Protection

800

Speed
Torque
Position

Pn403
Reverse Torque Limit

Torque limit

Too small a torque limit will

result in an insufficient torque

during acceleration and

deceleration.

Torque

Motor

speed