System Startup

5.2.1 MP940 Module

5-12

LED Indicator Specifications

The following table shows the 260IF LED indicator specifications.

Table 5.1 LED Indicator Specifications

∗ 1.

The offline status indicates the status during the time from when the

LED indicator test has been completed immediately after startup, until
the MAC ID overlapping check has been completed (approx. 2 s). The
online status indicates the status after the MAC ID overlapping check.

∗ 2.

If the error is caused by a disconnected network power supply, Auto-

matic Reset is activated even when a DeviceNet bus off error occurs.
NS lights red momentarily, and then turns OFF immediately. After the
power supply of the network has been recovered, NS flashes green.

Immediately after the power supply has been turned ON, the MS and NS LED indicators
will be tested for 1 second according to DeviceNet specifications. The status displayed by
this operation is shown in the following flowchart.

Fig 5.2 Display during LED Indicator Test

Name

Indicator

Color

Status

Meaning

MS

Red/Green

Unlit

Power not supplied to the Module

Lit green

Operating normally.

Lit red

Self-diagnosis error/WDT error

NS

Red/Green

Unlit

Power not supplied/Module is offline

*1

Flashing green

Module is online, but connection cannot be con-
firmed.

Lit green

Module is online and connection is confirmed.

Flashing red

DeviceNet not communicating

Lit red

Communications not possible (MAC ID over-
lapped)/Bus OFF error
WDT error

*2

NS

MS

Unlit

Unlit

Unlit

Unlit

Unlit

Green

Red

0.25 s

0.25 s

0.25 s

0.25 s

Green

Green

Red

Green

Green

Power supply is OFF.

Module

startup

LED indicator test starts.

1 s

LED indicator test completed