beautypg.com

Digital output circuits – Yaskawa MP940 User Manual

Page 117

background image

MP940 Functions

4.3.2 LIO Specifications

4-24

„

Digital Output Circuits

DO-07 is the conformity output signal when the CNTR fixed parameter

for the conformity detection function is set to enabling using the detec-
tion function.

A fuse is inserted in the output common line of the Output Modules as a protective circuit. If the out-
put short-circuit is incomplete, there is a risk that the fuse may not blow.

Item

Specifications

Number of Output
Points

8 pts./common

Output Format

Sinking outputs

Output Type

Transistor outputs

Isolation

Photocoupler isolation

Load Voltage

19.2 to 28.8 VDC
35 VDC (peak voltage)

Load Current

0.1 A/circuit; 0.8 A/common

ON Voltage

1.0 V max.

External Power
Supply

24 VDC ±20% at 15 mA

Output Protection

One fuse per common

Fuse Rating

1.5 A (opening time: 5 s max. at 3 A)

Response Time

OFF to ON

0.25 ms max.

ON to OFF

Digital Output
Circuit *

Register Number

OW0000 (default): Can be set on the Module Configuration Definition
Screen.

45

21

20

46

22

23

48

47

24

49

25

50

L

L

L

L

L

L

L

L

Fuse

Fuse

Extern

al outp

ut signal

Broken-fuse

detection cir-

cuit