Troubleshooting

9.1.3 Indicator Errors

9-4

„

LED Indicator Details

The following describes details and remedies for indicators showing operating status and

errors in the MP940.

Classifi-

cation

Indicator Name

Indicator Details

Remedy

RDY

RUN

ALM

BAT

Normal

Unlit

Unlit

Lit

Unlit

Hardware reset status

Normally the CPU activates within a second. If this sta-
tus continues for more than a second, the problem is a
user program error or hardware failure.
Troubleshoot system errors.

Unlit

Unlit

Unlit

Unlit

Initializing

Lit

Unlit

Unlit

Unlit

User program stopped (Offline
Stop Mode)

This status will occur if a program is stopped from the
CP-717 or by turning OFF the RUN switch.

Lit

Lit

Unlit

Unlit

User program executing nor-
mally

This status will occur during normal operation.

Error

Unlit

Lit

Lit

Unlit

Serious failure has occurred

See 9.2.2 Processing Flow When a System Error
Occurs
.

Lit

Unlit

Lit

Unlit

• Program memory initialization

incomplete

• Improper scan time setting

• Clear program memory from the System Definition

Screen on the CP-717.

• If this does not restore the system, then hardware has

probably failed.

Unlit

Unlit

Flashing

Unlit

Hardware errors
No. of flashes
2: RAM diagnosis error
3: ROM diagnosis error
4: CPU function diagnosis error
5: FPU function diagnosis error

Troubleshoot system errors.

Warning

-

-

-

Lit

Battery alarm

Replace the battery.

Lit

Lit

Lit

Unlit

Operation error

Refer to User Operating Error Status.

I/O error

Refer to System I/O Error Status.

Wrong interrupt occurs

System register warning
(no indicator display)

CP-717 connection data

See System Status in 9.2.4 System Register Configura-
tion.

Hardware status (power interrup-
tion, RUN/STOP, Test Mode,
etc.)

See System Status in 9.2.4 System Register Configura-
tion.