Led indicator details – Yaskawa MP940 User Manual
Page 349
Troubleshooting
9.1.3 Indicator Errors
9-4
LED Indicator Details
The following describes details and remedies for indicators showing operating status and
errors in the MP940.
Classifi-
cation
Indicator Name
Indicator Details
Remedy
RDY
RUN
ALM
BAT
Normal
Unlit
Unlit
Lit
Unlit
Hardware reset status
Normally the CPU activates within a second. If this sta-
tus continues for more than a second, the problem is a
user program error or hardware failure.
Troubleshoot system errors.
Unlit
Unlit
Unlit
Unlit
Initializing
Lit
Unlit
Unlit
Unlit
User program stopped (Offline
Stop Mode)
This status will occur if a program is stopped from the
CP-717 or by turning OFF the RUN switch.
Lit
Lit
Unlit
Unlit
User program executing nor-
mally
This status will occur during normal operation.
Error
Unlit
Lit
Lit
Unlit
Serious failure has occurred
See 9.2.2 Processing Flow When a System Error
Occurs.
Lit
Unlit
Lit
Unlit
• Program memory initialization
incomplete
• Improper scan time setting
• Clear program memory from the System Definition
Screen on the CP-717.
• If this does not restore the system, then hardware has
probably failed.
Unlit
Unlit
Flashing
Unlit
Hardware errors
No. of flashes
2: RAM diagnosis error
3: ROM diagnosis error
4: CPU function diagnosis error
5: FPU function diagnosis error
Troubleshoot system errors.
Warning
-
-
-
Lit
Battery alarm
Replace the battery.
Lit
Lit
Lit
Unlit
Operation error
Refer to User Operating Error Status.
I/O error
Refer to System I/O Error Status.
Wrong interrupt occurs
System register warning
(no indicator display)
CP-717 connection data
See System Status in 9.2.4 System Register Configura-
tion.
Hardware status (power interrup-
tion, RUN/STOP, Test Mode,
etc.)
See System Status in 9.2.4 System Register Configura-
tion.