Publication 1784-UM003A-EN-P – June 2003

Adding and Configuring Your 1784-PM02AE Motion Module 59

Major/Minor Fault Status

Internal State Status

This field displays the module’s current operational state.

• Self-test
• Flash update
• Communication fault
• Unconnected
• Flash configuration bad
• Major Fault
• Run mode
• Program mode
• (16#xxxx) unknown

If you selected the wrong module from the module selection tab, this field
displays a hexadecimal value. A textual description of this state is only given
when the module identity you provide is a match with the actual module.

Configured

This field displays a yes or no value indicating whether the module has been
configured by an owner controller connected to it. Once a module has been
configured, it stays configured until the module is reset or power is cycled,
even if the owner drops connection to the module.

Owned

This field displays a yes or no value indicating whether an owner controller is
currently connected to the module.

If you are configuring a:

This field displays one of the
following:

digital module

EEPROM fault
Backplane fault
None

analog module

Comm. Lost with owner
Channel fault
None

any other module

None
Unrecoverable
Recoverable